Permit Information
Permit NumberNAF17-00041
StatusFinaled
Name ABSOLUTE FIRE PROTECTION
Site Address 8250 MARIGOLD
Project NameEMERSON HOUSE ADDITION
Customer Number 
ePlanReviewNo
Description
[Emerson House Addition]
The fire sprinkler scope of work consists of a new addition to an existing facility. The fire protection piping will be connected to the existing systems. The wet system CPVC piping will be ran in the attic and tented. A galvanized dry pipe system will protect the attic. The attic has a steeply pitched roof and has a 1-hour wall separating it from the existing attic.

[NAF17-00010]
Permit to construct a 1,799 Sq.Ft. addition to an assisted living facility. This building is fully fire sprinklered with an approved fire alarm system. Separate Fire Permits WILL BE REQUIRED.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final9/25/20179/26/20179/26/2017ADONE
DetailsTroy Cobbley
Permit finaled
DOC - Permit Finaled  9/26/2017 DONE
DetailsRita DeYoung
Per Troy permit finaled
INSP-Final9/22/20179/25/20179/25/2017ACANC
DetailsTroy Cobbley
After ten am Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
INSP-Sprinkler Rough-in8/22/20178/23/20178/23/2017APASS
DetailsTroy Cobbley
Tie in piping is approved for cover. The fitting is going to repair the insulation/tenting in the new area. Per the general contractor the insulating contractor will tent the tie-ins. He will provide documentation to me when that work is done.
INSP-Sprinkler Rough-in/Hydro8/18/20178/22/20178/22/2017APASS
DetailsTroy Cobbley
24 hour are test passed for the new addition
INSP-Sprinkler Rough-in/Hydro8/18/20178/21/20178/21/2017APART
DetailsTroy Cobbley
24 hour air test started at 7:15 with 84psi on the guage.
INSP-Sprinkler Rough-in8/18/20178/18/20178/18/2017PPART
DetailsTroy Cobbley
Tenting passed and wet system piping rough-in passed. Piping can be covered as marked on the city approved plans. Will need another cover inspection once the two tie -ins are complete. Phone #: ###-#### Inspection requested via web by Sam Ball
INSP-Sprinkler Rough-in/Hydro8/14/20178/14/20178/14/2017PPART
DetailsJim Page
Hydrostatic test complete for both wet and dry systems in area of work. Rough to cover inspection for dry systen complete, dry system is approved for cover. Rough in inspection complete for wet system area of work, wet system piping cannot be covered until tenting of wet system overhead fire sprinkler piping is complete and inspected.