Permit Information
Permit NumberNAF18-00049
StatusFinaled
Name VIKING AUTOMATIC SPRINKLER CO
Site Address 610 E 42ND ST
Project NameBLDFY2018-0058
Customer Number 
ePlanReviewNo
Description
BLDFY2018-0058
[Boys & Girls Club]
The fire sprinkler scope of work consists of a new addition and a remodel of the existing kitchen. The existing 2” primary and secondary mains will be extended and four new branch lines added. The kitchen will have a loop installed.
[BLDFY2018-0058]
Permit to remodel existing kitchen and construct a new 6,600 sq.ft. addition which includes a cafeteria for use by Boys & Girls club and partner public schools. This building is fully fire sprinklered with a fire alarm system. Separate permits will be required for necessary modifications to the existing building fire protection systems, including any commercial kitchen hood suppression systems; as regulated by North Ada County Fire Protection District.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final7/30/20187/31/20187/31/2018ADONE
DetailsTroy Cobbley
Permit finaled

Call prior to going Phone #: 2088706532 >> Inspection requested via mobile web by Roy Fouts
DOC - Permit Finaled  7/31/2018 DONE
per troy cobbley
INSP-Final7/23/20187/24/20187/24/2018PFAIL
DetailsTroy Cobbley
Not ready for final yet. Need tape removed from uprights in the Cafeteria and Restrooms, need pendant heads installed shown on plans in the Dry Storage Room, need verification of combustible concealed space coverage over the existing kitchen. Hydro test passed for the new Kitchen area.

Call prior to going Phone #: 2088901055 >> Inspection requested via mobile web by Zack Grasmick
INSP-Final7/18/20187/20/20187/20/2018PFAIL
DetailsTroy Cobbley
Not ready for final. Still need hydro test for the new piping in the Kitchen and the ceiling tile needs to be removed so that a rough-in inspection can be done for the sprinkler piping in the Kitchen. Need ceiling tile installed in the clouds in the Dining area and all of the upright sprinklers in the Dining need the covers off the sprinklers.

Call prior to going Phone #: 2088903587 >> Inspection requested via mobile web by Raul Munoz
INSP-Final7/18/20187/20/20187/18/2018PCANC
DetailsTroy Cobbley
Call prior to going Phone #: 2088706532 >> Inspection requested via mobile web by Roy Fouts Inspection cancelled via mobile web on Wednesday, July 18, 2018.
INSP-Sprinkler Rough-in/Hydro6/12/20186/13/20186/13/2018APASS
DetailsTroy Cobbley
Hydro test for the new piping in the Dining area passed.

Call prior to going Phone #: 2085611337 >> Inspection requested via mobile web by Gabe
INSP-Sprinkler Rough-in/Hydro6/11/20186/12/20186/12/2018AFAIL
DetailsTroy Cobbley
Hydro test failed again due to visible leak

Call prior to going Phone #: 2085611337 >> Inspection requested via mobile web by Gabe
INSP-Sprinkler Rough-in/Hydro6/8/20186/11/20186/11/2018AFAIL
DetailsTroy Cobbley
Overhead hydro test failed due to puddle on floor and loss of pressure at the guage.

Phone #: 2088706532 >> Inspection requested via mobile web by Roy
INSP-Sprinkler Rough-in/Hydro6/7/20186/7/20186/7/2018PPASS
DetailsTroy Cobbley
The combustilbe concealed space above the Dining area Restrooms has been filled with insulation and is ok for coverl.


Call prior to going Phone #: 2088706532 >> Inspection requested via mobile web by Roy
INSP-Sprinkler Rough-in/Hydro5/29/20185/30/20185/31/2018PCANC
DetailsTroy Cobbley
Not ready for an inspection or hydro test yet. I noted non-rated wood being used which is creating combustible concealed spaces that do not have sprinkler protection.


Call prior to going Phone #: 2085611337 >> Inspection requested via mobile web by Gabe