Permit Information
Permit NumberNAF19-00011
StatusIssued
Name NACFR
Site Address 2950 W HIDDEN SPRINGS DR
Project NameNAC
Customer Number 
ePlanReviewNo
Description
Installing a new sprinkller system above and below the ceiling. 9-12 slope on the roof. We will be installing four dry pendents in the eaves outside.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Sprinkler Rough-in/Hydro3/19/20193/19/20193/19/2019PPASS
DetailsTroy Cobbley
Above ground hydro test witnessed with no visible pressure loss at the guage.


Call prior to going Phone #: 7753857345 >> Inspection requested via mobile web by Roy Nelsen
INSP-Sprinkler Rough-in/Hydro3/12/20193/13/20193/13/2019AFAIL
DetailsTroy Cobbley
Overhead hydro test failed again due to visible loss on guage.

Call prior to going Phone #: 7753857345 >> Inspection requested via mobile web by Roy Nelsen
INSP-Sprinkler Rough-in/Hydro3/11/20193/12/20193/12/2019AFAIL
DetailsTroy Cobbley
Overhead hydro failed due to visible loss on pressure guage.

Call prior to going Phone #: 7753857345 >> Inspection requested via mobile web by Roy Nelsen
INSP-Sprinkler Rough-in/Hydro3/8/20193/11/20193/11/2019APASS
DetailsTroy Cobbley
Rough-in passed for the Riser room and piping can be covered. Dry pendant has been relocated in the northwest canopy. Not ready for hydro until water is turned on.
INSP-Sprinkler Rough-in3/5/20193/6/20193/6/2019ACANC
DetailsTroy Cobbley
Call prior to going Phone #: 2083621888 >> Inspection requested via mobile web by Dan
INSP-Sprinkler Rough-in3/5/20193/5/20193/5/2019PPASS
DetailsTroy Cobbley
Rough-in passed. Piping can be covered. One dry pendant is overspaced on the west end of the north side exterior soffit.


As late as possible Phone #: 2083621888 >> Inspection requested via mobile web by Dan Buccino
INSP-Sprinkler Rough-in3/4/20193/6/20193/5/2019ACANC
DetailsTroy Cobbley
As early as possible Phone #: 7753857345 >> Inspection requested via mobile web by Roy Inspection cancelled via mobile web on Tuesday, March 05, 2019.
INSP-Sprinkler Rough-in2/28/20193/1/20193/1/2019APASS
DetailsTroy Cobbley
Todays inspection was for hanger placement prior to covering by foam insulation. Hangers appear ok.
Call prior to going Phone #: 2088719664 >> Inspection requested via mobile web by Jeff