Permit Information
Permit NumberNAF19-00019
StatusFinaled
Name ABSOLUTE FIRE PROTECTION
Site Address 5655 N GLENWOOD ST Unit: 101/102
Project NameGC
Customer Number 
ePlanReviewNo
Description
(Ashland Creek) This a new sprinkler system in a new single level building. The areas below the ceiling are protected by a tented wet system. The attic is protected by a dry pipe system. The upright sprinklers on the dry system are 4.2k with pipe that is corrosion resistant per 8.3.4.4.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final10/8/201910/8/201910/8/2019PDONE
DetailsTroy Cobbley
Permit finaled.

Phone #: ###-#### Inspection requested via web by Sam Ball
DOC - Permit Finaled  10/8/2019 DONE
Per Troy C, 10/8/19 Final inspection
INSP-Final9/18/20199/19/20199/19/2019AFAIL
DetailsTroy Cobbley
Can final when heat is provided and the plastic is attached to the trusses (repaired) and insulation is provided at these patched areas. Phone #: ###-#### Inspection requested via web by Sam Ball
INSP-Final8/21/20198/22/20198/22/2019PPART
DetailsTroy Cobbley
Sprinkler work is complete. Temporary per Boise Fire. Permit can be finaled when the shell/core permit is finaled.

Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Brian
INSP-Final8/20/20198/21/20198/21/2019AFAIL
DetailsTroy Cobbley
There were problems with the fire alarm system which prevented testing of the sprinkler system. No testing performed.
Phone #: ###-#### Inspection requested via web by Sam Ball
INSP-Sprinkler Rough-in/Hydro8/6/20198/7/20198/7/2019APASS
DetailsTroy Cobbley
24 hour air test on dry system and hydrostatic test on wet system witnessed with no pressure loss. Phone #: ###-#### Inspection requested via web by Sam Ball
INSP-Conference8/5/20198/6/20198/6/2019PDONE
DetailsTroy Cobbley
Myself, sam and the job superintendant spoke about a temporary occupancy for the two tenants until a third middle tenant is found with-in the next couple months. I deferred the request to the fire dept.

Call prior to going Phone #: 2085731293 >> Inspection requested via mobile web by Sam
INSP-Sprinkler Rough-in/Hydro8/5/20198/6/20198/6/2019PPART
DetailsTroy Cobbley
24 hour air test started on the dry system with 41psi on the guage.

Call prior to going Phone #: 2085731293 >> Inspection requested via mobile web by Sam
INSP-Sprinkler Rough-in7/11/20197/11/20197/11/2019PPASS
DetailsTroy Cobbley
Head added to the concealed area above fire place. Tenting passed. Piping for the west side tenant space can be covered. The center tenant space can not be covered until a tenting inspection has been completed.
INSP-Final7/11/20197/11/20197/11/2019PCANC
DetailsTroy Cobbley
Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Brian Inspection cancelled via mobile web on Thursday, July 11, 2019.
INSP-Sprinkler Rough-in6/25/20196/25/20196/25/2019PPART
DetailsJim Page
Tenting inspection for east side tenant space complete, all tenting in place for east side tenant at time of inspection, east side tenant space approved for cover.

Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Brian
INSP-Sprinkler Rough-in6/21/20196/24/20196/24/2019APASS
DetailsJim Page
Previously noted items have been corrected.

Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Bryan
INSP-Sprinkler Rough-in6/19/20196/20/20196/19/2019AFAIL
DetailsTroy Cobbley
EQ bracing on wet system main needs to be changed to what was approved. Dry system ok **MAS**
Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Brian
INSP-Sprinkler Rough-in/Hydro6/19/20196/19/20196/19/2019PPASS
DetailsTroy Cobbley
Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Brian
INSP-Supply line flush5/17/20195/20/20195/20/2019APASS
DetailsTroy Cobbley
Underground supply line flush witnessed. Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Brian
INSP-Sprinkler Rough-in/Hydro4/11/20194/12/20194/12/2019APASS
DetailsTroy Cobbley
The underground hydro test was witnessed with no pressure loss.
Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Brian
INSP-Sprinkler Rough-in3/26/20193/27/20193/27/2019APASS
DetailsTroy Cobbley
Underground supply line cover passed.


Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Brian
INSP-Sprinkler Rough-in3/26/20193/26/20193/26/2019PCANC
DetailsTroy Cobbley
Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Brian