Permit Information
Permit NumberNAF19-00038
StatusFinaled
Name NACFR
Site Address 2900 CHINDEN BLVD
Project NameGC
Customer Number 
ePlanReviewNo
Description
Upgrade of 2 existing hood systems with duct and plenum coverage.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final6/5/20196/6/20196/6/2019ADONE
DetailsTroy Cobbley
Permit finaled. Suppression system function witnessed.


Call prior to going Phone #: 2086317804 >> Inspection requested via mobile web by Nate
DOC - Permit Finaled  6/6/2019 DONE
DetailsTroy Cobbley
as per Troy C. doc final-final insp passed
INSP-Final5/1/20195/2/20195/2/2019AFAIL
DetailsTroy Cobbley
Plan mods are needed for one hood due to changed nozzles numbers and one additional nozzle at the grill. All nozzles/piping needs braced and tightened so it does not spin in the fittings. Lights need to be repaired so shut off upon activation of the suppression system can be verified.

Call prior to going Phone #: 2086319935 >> Inspection requested via mobile web by Nate