Permit Information
Permit NumberNAF19-00070
StatusFinaled
Name ABSOLUTE FIRE PROTECTION
Site Address 5024 W CHINDEN BLVD
Project NameGC
Customer Number 
ePlanReviewNo
Description
**PLAN MODIFICATION FOR MODULAR MRI FIRE SPRINKLER SYSTEM 10-23-19** Tie-in of a new MRI modular with factory installed fire sprinkler.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final10/25/201910/25/201910/25/2019PDONE
DetailsJim Page
Previously noted items have been corrected, final fire sprinkler inspection for area of work complete.

Will be done by3:30pm Phone #: ###-#### Inspection requested via web by Sam Ball
INSP-Sprinkler Rough-in/Hydro10/25/201910/25/201910/25/2019PDONE
DetailsJim Page
Hydrostatic for overhead fire sprinkler piping modifications complete, no pressure loss observed.

DOC - Permit Finaled  10/25/2019 DONE
per jim page
INSP-Final10/11/201910/14/201910/15/2019PCANC
DetailsTroy Cobbley
Phone #: ###-#### Inspection requested via web by Sam Ball
INSP-Sprinkler Rough-in10/11/201910/14/201910/15/2019PFAIL
DetailsTroy Cobbley
Per the state of idaho and the boise fire dept the fier sprinkler system/addition is required to meet mimimum code as adopted by the state of idaho. All corrections as noted need to be addressed which include plan modifications for pipe size changes, pipe routing changes, obstructions, combustible concealed spaces, hanger issues, branch line restraint issues.....ect

Phone #: ###-#### Inspection requested via web by Sam Ball
INSP-Final10/11/201910/14/201910/11/2019ACANC
DetailsTroy Cobbley
Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
INSP-Sprinkler Rough-in10/11/201910/14/201910/11/2019ACANC
DetailsTroy Cobbley
Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
INSP-Final8/21/20198/22/20198/22/2019ACANC
DetailsTroy Cobbley
Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Brian