INSP-Final | 11/25/2019 | 11/26/2019 | 11/26/2019 | A | DONE |
Troy Cobbley
|
|
|
Permit finaled.
Cal Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
DOC - Permit Finaled | | | 11/26/2019 | | DONE |
|
|
|
per troy
|
INSP-Final | 11/25/2019 | 11/25/2019 | 11/25/2019 | P | CANC |
Troy Cobbley
|
|
|
Call Anthony before heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|
INSP-Sprinkler Rough-in/Hydro | 9/3/2019 | 9/4/2019 | 9/4/2019 | A | PASS |
Troy Cobbley
|
|
|
Overhead rough-in, tenting and hydro passed. Piping is ok for cover. Well supply piping not provided yet.
Call prior to going Phone #: 2083910988 >> Inspection requested via mobile web by Anthony Minichiello
|
INSP-Sprinkler Rough-in/Hydro | 9/3/2019 | 9/3/2019 | 9/3/2019 | P | PART |
Troy Cobbley
|
|
|
Rough-in passed. Tenting has not been completed above the stairs at the second floor. Tenting passed in other areas. Piping can be covered except at the second floor stairs. No water supply yet. No hydro yet.
Call prior to going Phone #: 2083910988 >> Inspection requested via mobile web by Anthony
|
INSP-Sprinkler Rough-in/Hydro | 8/27/2019 | 8/27/2019 | 8/27/2019 | P | FAIL |
Troy Cobbley
|
|
|
Need as-built/plan mods showing the actual pipe routing, need the riser piping addressed that is exposed as discussed, need tenting inspection. No piping can be covered.
Call prior to going Phone #: 2083910988 >> Inspection requested via mobile web by Anthony
|