Permit Information
Permit NumberPLM15-02821
StatusFinaled
Name MERIDIAN PLUMBING CO INC
Site Address 8505 W OVERLAND RD
Project Name 
Customer Number158047
ePlanReviewNo
Description
Alteration: TENANT IMPROVEMENT: FOR BATHROOM & BREAKROOM REMODEL
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/7/201510/7/201510/7/2015PPASS
DetailsJim Little
final reinspect Phone #: ###-#### Inspection requested via web by Chris Field
Final10/6/201510/6/201510/6/2015PFAIL
DetailsJim Little
TENANT IMPROVEMENT FINAL TRIM Phone #: ###-#### Inspection requested via web by Chris Field
>caulk around mop sink
>add temp limiting device that is ASSE 1070 certified on both lavs to limit hot water to 120 degrees or less. per 413.1 upc
Final10/6/201510/6/201510/6/2015PFAIL
DetailsJim Little
TENANT IMPROVEMENT FINAL TRIM Phone #: ###-#### Inspection requested via web by Chris Field
>caulk around mop sink
>add temp limiting device that is ASSE 1070 certified on both lavs to limit hot water to 120 degrees or less. per 413.1 upc
Plumbing Rough-in9/16/20159/16/20159/16/2015PPASS
DetailsJim Little
STEVE RADY, CONTRACTOR. Phone #: ###-#### Inspection requested via web by Chris Field
Plumbing Rough-in9/15/20159/15/20159/15/2015PFAIL
DetailsJim Little
STEVE RADY, CONTRACTOR, ###-####
Phone #: ###-#### Inspection requested via web by Chris Field
>1 Need permanent glue caps on demoed plumbing.
>2 Santee not approved for horizontal use @ wb
>3 must be 6" above flood level rim before turning horizontal @ mop sink upc 905.3
>4 leak at nipple on hot side of wh loop.
>5 retest and re inspect
Groundwork8/24/20158/25/20158/25/2015APASS
DetailsJim Little
steve rady
Phone #: ###-#### Inspection requested via web by Chris Field
Groundwork8/24/20158/24/20158/24/2015PFAIL
DetailsJim Little
GROUNDWORK Phone #: ###-#### Inspection requested via web by Chris Field
>DWV test fail, need 10' head
>Wye at mop sink for vent installed backwards
Groundwork8/20/20158/21/20158/21/2015PNR
DetailsJim Little
STEVE RADY, ###-#### Phone #: ###-#### Inspection requested via web by Chris Field