Permit Information
Permit NumberPLM16-00473
StatusFinaled
Name DOUBLE A PLUMBING ENT LLC
Site Address 8017 W FAIRVIEW AVE
Project NameLa Ranchera Market
Customer Number 
ePlanReviewNo
Description
install (3) floor sinks, toilets, water heater, prep sinks
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/19/20165/19/20165/19/2016PPASS
DetailsJim Little
Juan Phone #: ###-####
Final5/18/20165/18/20165/18/2016PNR
DetailsJim Little
Juan Phone #: ###-####
Final5/17/20165/17/20165/17/2016PFAIL
DetailsJim Little
Juan Phone #: ###-####
>Install ASSE 1070 tempering device on lavs in bathrooms.
>T&P on water heater needs a 1" airgap
>open floor @ ejector pump to be able to see tank lid for inspection.
Plumbing Rough-in3/18/20163/18/20163/18/2016PPASS
DetailsJim Little
Juan Phone #: ###-####
Plumbing Rough-in3/17/20163/17/20163/17/2016PPART
DetailsJim Little
Juan Phone #: ###-####
>need to test ejector line
>need to add nailplates
Groundwork3/1/20163/1/20163/1/2016PPASS
DetailsJim Little
>G/I test ok
Groundwork2/26/20162/29/20162/29/2016APASS
DetailsJim Little
Juan Phone #: ###-####
>gw inside ok
>start 24hr test on G/I
Groundwork2/26/20162/26/20162/26/2016PFAIL
DetailsJim Little
Juan Phone #: ###-####
>section backgraded after new 4x3 wye installed
>neeed approved band @ 4" abs to cast iron
Groundwork2/25/20162/25/20162/25/2016PFAIL
DetailsJim Little
Juan Phone #: ###-####
>ejector pumps needs to tie into 4"
>fix backgraded section
>need 4" c/o on G/I
>move 3" vent to outlet of G/I
>need C/O on outlet of G/I
>restest