Permit Information
Permit NumberPLM16-00761
StatusFinaled
Name MANDERSCHEID JACQUELINE
Site Address 12561 W BOWMONT CT
Project Name 
Customer Number 
ePlanReviewNo
Description
Homeowner Online - Alteration or Repair: Adding toilet, bathroom sink, utility sink and floor drain.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/21/20167/22/20167/22/2016APASS
DetailsJim Little
Jim, toilet, utility sink, floor drain in the aux. bldg functional ; ready for final inspection.
I decided not to connect the sink in the half-bath. Request your final inspection . Thank you. Jacqueline Manderscheid Phone #: ###-#### Inspection requested via web by Jacqueline Manderscheid
>only wc and utility sink set at time of final, homeowner says she is not doing the lav or floor drain.
Plumbing Rough-in4/12/20164/12/20164/12/2016PPASS
DetailsJim Little
Jacqueline Phone #: ###-####
>crawl space ri ok
Plumbing Rough-in3/15/20163/16/20163/16/2016PPART
DetailsJim Little
Jacqueline Phone #: ###-####
>aux bld ri ok
>crawl space corrections still need to be inspected
Plumbing Rough-in3/11/20163/14/20163/14/2016AFAIL
DetailsJim Little
Jacqueline Phone #: ###-####
>both cleanouts at sinks leaking, fix and retest
Water and/or Sewer3/4/20163/4/20163/4/2016PFAIL
DetailsJim Little
EXTEND waste piping inside existing auxiliary building,
CHANGE supply piping inside building from 1/2'' to 3/4'',
ADDED tixtures: toilet, floor drain, bathroom sink
CHANGED fixture to barn sink below window
UNDERGROUND and rough-in inspection on test today.Jacqueline Phone #: ###-#### Inspection requested via web by Jacqueline Manderscheid
CRAWL SPACE:
1.hang every 4 feet
2. grade 1/4" per foot
3. use approved glue
4.install 4" c/o
5. test @ 5 psi
AUX BLDG:
1. transition glue not approved in bldg
2. grade 1/4" per foot
3. must be 6" above flood rim before turning horizontal
4. santee not approved ftg on wc vent
5. need full size c/o at upper terminal
6. test @ 5 psi
7. pex joints not approved under slab
8. retest water