Permit Information
Permit NumberBLD18-02821
StatusFinaled
Name PARADIGM CONSTRUCTION COMPANY LLC
Site Address 3088 E WINDSONG DR
Project NameChristie Residence
Customer Number 
ePlanReviewNo
Description
***10/30/19 PLAN MODIFICATION FOR NEW GRADING PLAN*** This structure is required to be fully fire sprinklered in compliance with NFPA 13D**Permit for the construction of a new 4097 sq. ft., two story (lower floor is 1600 sq. ft., main floor level is 2497 sq. ft.) single family dwelling with 4 bedrooms, 3.5 bathrooms, approximately 550 sq. ft. of covered patio/porch and a 1656 sq. ft. attached garage per the approved plans and any notations. Prescriptive Energy Compliace. R-1A/DA zoning and setbacks per planning. ***RDP***
A letter from the applicant’s geotechnical engineer indicating that the footing/column subgrade is acceptable must be approved by Public Works prior to scheduling a footing inspection. Please e-mail the stamped inspection approval letter to mjannusch@cityofboise.org and allow 24 hours for subgrade approval processing. Call Melissa Jannusch at 208-608-7168 with questions.

Prior to obtaining a final for the permit, the roof storm drainage system must be inspected by Public Works. Call Melissa Jannusch at 208-608-7168.

The final inspection of the site grading and drainage work shall be done by the design engineer. Written approval shall be submitted to Boise Public Works prior to the issuance of the building final.

An erosion and sediment control site preparation inspection is required for this site. The site preparation inspection takes place after all required erosion and sediment control best management practices have been installed and BEFORE any earthwork takes place. Call 208-608-7070 to schedule an inspection.
Contact Information
See Activities list for contact information
Color Key
Current location of plans being reviewed:  
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final11/4/201911/4/201911/5/2019PPASS
DetailsBrandon Shaw
Call when on the way to meet // Matt Phone #: ###-####
DOC - Permit Finaled11/5/201911/5/201911/5/2019PPASS
DetailsBrandon Shaw
PubWorks Occupancy Approval11/5/201911/5/201911/5/2019 DONE
DetailsMelissa Jannusch
A letter from the applicant’s design professional indicating that the final grading and drainage is acceptable has been received by Public Works. Final occupancy may be approved by the building department. Melissa Jannusch ###-####.

OVERRIDE  11/4/2019  
Plan assigned to (RDP)10/30/201910/30/201911/4/2019 DONE
DetailsRob Patrick
11/18 sfd L2 PAPER...11/1 delivered plans to Melissa
Routing PW Grading-Hillside11/4/2019 11/4/2019 PASS
DetailsMelissa Jannusch
PLAN MOD APPROVED.
Routing - PUBLIC WORKS11/4/2019 11/4/2019 PASS
DetailsCandy A. Nichols
Routing - PLAN CHECK11/4/2019 11/4/2019 PASS
DetailsRob Patrick
Grading Plan change only. Melissa review.
PLANS/APPL TAKEN TO FRONT DESK  11/4/2019 DONE
DetailsRob Patrick
Permit Ready to Issue  11/4/2019 DONE
plan mod
CHANGE STATUS TO (ISS)  11/4/2019 DONE
PLAN MOD
Plan Reviewer's activity  11/1/2019  
Delivered entire plan set to Melissa for her review.
BLD-Conference10/29/201910/30/201910/30/2019ADONE
DetailsBrandon Shaw
please call 1/2 hr prior. Was hoping to do a courtesy final. Thanks Jim Phone #: ###-#### Inspection requested via web by James Larkin
Plan Modification Accepted  10/30/2019 DONE
James from Paradigm contruction submitted 3 paper copies of the original grading plan and the modified grading plan - specified on the title page. 6 copies in all
BLD-Energy code compliance6/26/20196/27/20196/27/2019PPASS
DetailsBrandon Shaw
Please call 1/2 hr prior. Thanks Jim Phone #: ###-#### Inspection requested via web by James Larkin
BLD-Framing/Rough-in6/25/20196/25/20196/25/2019PPASS
DetailsBrandon Shaw
please call 1/2 hr prior Thanks Jim Phone #: ###-#### Inspection requested via web by James Larkin
FIRE-Supply Line Cover6/19/20196/19/20196/19/2019ACANC
DetailsJim Page
Tenting inspection needs to be requested by the fire sprinkler contractor, this request is cancelled and future fire sprinkler related inspection must be done under associated FIR permit.

Insulation or tent over fire sprinkler piping that is in attic area of project. Not sure if we ordered the correct inspection? Phone #: ###-#### Inspection requested via web by James Larkin
BLD-Wall cover6/13/20196/14/20196/14/2019APASS
DetailsMike Jordan
Fire protection on Soffit cans. 2 layers of type x 5\8. Phone #: ###-#### Inspection requested via web by James Larkin
BLD-Wall Bracing6/3/20196/3/20196/3/2019PPASS
DetailsJim Storey
Jim Phone #: ###-####
BLD-Wall Bracing5/24/20195/28/20195/28/2019PCANC
DetailsBrandon Shaw
Please call 1/2 hr prior. Phone #: ###-#### >> Inspection requested via web by James Larkin Inspection cancelled from web by: James Larkin
BLD-Wall Bracing5/23/20195/24/20195/24/2019ACANC
DetailsBrandon Shaw
Please call 1/2 her prior. Thanks Jim Phone #: ###-#### >> Inspection requested via web by James Larkin Inspection cancelled from web by: James Larkin
BLD-Wall Bracing5/22/20195/23/20195/23/2019PCANC
DetailsBrandon Shaw
Please Call 1/2 prior Phone #: ###-#### >> Inspection requested via web by James Larkin Inspection cancelled from web by: James Larkin
BLD-Foundation4/26/20194/29/20194/29/2019APASS
DetailsDave Hannah
Edgar- foundation wall Phone #: ###-####
BLD-Footing4/23/20194/23/20194/23/2019PPASS
DetailsBrandon Shaw
edgir Phone #: ###-####
BLD-Footing4/22/20194/22/20194/22/2019PFAIL
DetailsJim Storey
retaining wall // Edgar Phone #: ###-#### no vert steel// bar in dirt at steps/ no plans on site.
BLD-Foundation2/1/20192/1/20192/1/2019PPASS
DetailsBrandon Shaw
wall- Ben Phone #: ###-####
BLD-Footing1/18/20191/18/20191/18/2019APASS
DetailsBrandon Shaw
Retaining wall footings
BLD-Foundation12/10/201812/11/201812/11/2018PCANC
DetailsBrandon Shaw
Please call 1/2 hr prior. Thanks Jim Phone #: ###-#### Inspection requested via web by James Larkin
BLD-Foundation12/10/201812/11/201812/11/2018APASS
DetailsBrandon Shaw
Work in progress...
Frost protection is reqired
BLD-Footing11/28/201811/28/201811/28/2018PPASS
DetailsBrandon Shaw
Work in progress
PubWorks Subgrade Approval11/28/201811/28/201811/28/2018 DONE
DetailsMelissa Jannusch
A letter from the applicant’s geotechnical engineer indicating that the footing/column subgrade is acceptable has been received by Public Works. Footing inspection may be scheduled with the Building Department. Melissa Jannusch ###-####.
BLD-Footing11/27/201811/27/201811/27/2018PNR
DetailsBrandon Shaw
Need soil sub-grade submitted and approved by PW...
BLD-Footing11/26/201811/27/201811/27/2018ACANC
DetailsBrandon Shaw
Please call 1/2 hr prior. Thanks Jim Phone #: ###-#### >> Inspection requested via web by James Larkin Inspection cancelled from web by: James Larkin
Issue PAID IN FULL permit  10/16/2018 DONE
OVERRIDE  10/1/2018  
Plan assigned to (RDP)8/13/20188/13/201810/1/2018 DONE
DetailsRob Patrick
08/30 sfd L2 Paper...8/28 Failed: Multiple Corrections Required...9-14 Delivered to Melissa for review
Telephone call  10/1/2018 DONE
Called James to advise permit is ready pending GC form and gave fees due
Permit Ready to Issue  10/1/2018 DONE
Need - met
GC Form ( RCE number doesn't match GC name)
Routing PW Grading-Hillside10/1/2018 10/1/2018 PASS
DetailsMelissa Jannusch
A letter from the applicant’s geotechnical engineer indicating that the footing/column subgrade is acceptable must be approved by Public Works prior to scheduling a footing inspection. Please e-mail the stamped inspection approval letter to mjannusch@cityofboise.org and allow 24 hours for subgrade approval processing. Call Melissa Jannusch at ###-#### with questions.

Prior to obtaining a final for the permit, the roof storm drainage system must be inspected by Public Works. Call Melissa Jannusch at ###-####.

The final inspection of the site grading and drainage work shall be done by the design engineer. Written approval shall be submitted to Boise Public Works prior to the issuance of the building final.

Routing - PUBLIC WORKS10/1/2018 10/1/2018 PASS
DetailsMorgan Webb
Routing - PLAN CHECK10/1/2018 10/1/2018 PASS
DetailsRob Patrick
Case Summary (BLD)  10/1/2018 DONE
DetailsRob Patrick
PLANS/APPL TAKEN TO FRONT DESK  10/1/2018 DONE
DetailsRob Patrick
Inspection Record Card- Bld  10/1/2018 DONE
Plan Reviewer's activity  9/28/2018  
Took 2 plan sets and 2 new engineering document sets to Melissa.
Route to Impact Fee Review9/25/20189/28/20189/26/2018 PASS
DetailsEric Bilimoria
Initial residential review of new SFD permits requested for now.
Routing - FIRE9/25/20189/25/20189/25/2018 PASS
DetailsErika Akin
Attached comments to case
Routing - PLAN CHECK9/25/2018 9/25/2018 FAIL
DetailsRob Patrick
Foundation calcs were supplied on 2012 IBC software. Emailed for new engineering docs.
Plan resubmittals received  9/25/2018 DONE
received two copies of structual calc package; taken to Rob Patrick
Routing PW Grading-Hillside9/21/2018 9/21/2018 FAIL
DetailsMelissa Jannusch
Retaining wall calculation corrections requested via e-mail to applicant.
Plan Reviewer's activity  9/14/2018  
DetailsRob Patrick
Delivered Plan set to Melissa for her review.
Plan resubmittals received  9/12/2018 DONE
Two copies on small site plan, two copies of Structural Calcs and two full new copies of plans sheets 1-7. taken to Rob
1st review completed  8/28/2018 FAIL
DetailsRob Patrick
Routing - PLAN CHECK8/27/2018 8/28/2018 FAIL
DetailsRob Patrick
Multiple corrections Required
Routing - FIRE8/23/20188/13/20188/27/2018 FAIL
DetailsErika Akin
Attached comments to case and plans and emailed applicant
Plan Reviewer's activity  8/27/2018  
8/27 Delivered paper plan set and documents to Troy for mechanical review.
Routing - MECHANICAL  8/27/2018 PASS
DetailsTroy James
Routing - PLANNING  8/27/2018 PASS
Routing - Erosion and Sediment8/23/2018 8/23/2018 PASS
DetailsAndy J. Long
ESC site map and project narrative approved. Certified RP & PD. Site preparation inspection is required prior to earthwork.
Routing PW Grading-Hillside8/14/2018 8/23/2018 FAIL
DetailsMelissa Jannusch
Retaining walls need corrections. Have contacted Kaleb Jones at Performance engineering and requested approval from the geotech for bearing capacity or updates to calculations --MMJ
Routing - PUBLIC WORKS8/23/2018 8/23/2018 FAIL
DetailsMorgan Webb
Routing PW Sewer Rating8/14/2018 8/14/2018 PASS
DetailsRachael Beierle
Routing - Addressing8/13/2018 8/14/2018 PASS
DetailsDoug Chausow
Plans ACCEPTED BY PLAN TECH  8/13/2018 DONE
Intake Approval  8/13/2018 PASS
Recd Pcfee & Taken To Pln CK  8/13/2018 DONE
Intake Approval  8/6/2018 FAIL
DetailsChristina Prado
Need CFH approval letter, ESC Narrative
Application received 8/6/2018   
Routing - PUBLIC WORKS9/21/2018   FAIL
SEE HILLSIDE FOR FAIL.