Permit Information
Permit NumberBLD19-00336
StatusFinaled
Name SADI HARP
Site Address 2530 S BROADWAY AVE
Project NameCovered in Love Preschool
Customer Number 
ePlanReviewNo
Description
(COVERED IN LOVE PRESCHOOL) Permit to occupy a portion of an existing educational facility for a daycare. There is no new work being completed under this permit as the current configuration is remaining and is compliant. This permit was required due to the use as a daycare. This facility was previously regulated by the building code as an E occupancy and the new daycare is also being evaluated as an E occupancy with no children under the age of 2 1/2 years. This area was remodeled under BLD98-03768 which brought the space into compliance as an E-1 occupancy. Attached is a recent fire department inspection indicated the area being used as a daycare is in compliance. This building is fully fire alarmed but is not fire sprinklered. Any alterations to the alarm system will require a separate permit and shal comply with NFPA 72 as required by the fire department. There is no change in occupancy under this permit. CDM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Meeting  7/16/2019 DONE
an email came in for the final values but it was sent to the cusotmer by mistake. The value was only $501.00.
First Notice 5/13/20197/10/2019 DONE
mailed 7-11 to sadi harp
BLD-Final5/2/20195/3/20195/3/2019PPASS
DetailsJim Storey
Sadie Phone #: ###-####
FIRE-Final Inspection5/2/20195/3/20195/3/2019APASS
DetailsMark Scharfen
Conducted fire life safety. Extinguishers, exit lighting and smoke detectors all in place and functional. repair on fire alarm has been done. passed life safety.

Sadie Phone #: ###-####
Permanent Occupancy  5/3/2019 DONE
BLD-Conference4/9/20194/10/20194/10/2019APASS
DetailsJim Storey
Jeff Phone #: ###-#### final ok pending fire
FIRE-Conference4/9/20194/9/20194/9/2019PDONE
DetailsJim Page
Fire conference complete, fire alarm notification throughout the building appears to be corridor notification and corridor only and the fire alarm is not monitored (Never has been based on the conversation with the tenants, which could have been code compliant on initial install). Based on my conversation with Ron Johnson the audio visual device in the "Little Rascals" room can be removed based on the fact the notification is in the corridor and this room is no longer part of a corridor. Stand-alone smoke detectors will need to be added per note number 7 of the Building fire code review comments to meet the requirement of each room having smoke detector coverage outside of the corridor. Door hardware will be changed to be code compliant and the blocked exit light will either be relocated or a new exit light will be added.
BLD-Conference3/27/20193/27/20194/1/2019PCANC
DetailsJim Storey
Jennifer or Jeff or ###-#### sadie Phone #: ###-####
Plan Reviewer's activity  3/21/2019 DONE
DetailsMark Scharfen
Ron/Jim,

If you haven’t already you will be getting an email from Collin looking to set up a conference regarding this permit. They converted a section of their un sprinkled building into a day care area, adding a door in the corridor to separate the area as well as a short wall separating the entry to one of the class/play rooms with a small door. There will be no children under 2 ½ in the new area, but it will not be part of the school. The plans were paper plans and very limited but the general notes on smoke detectors, exit hardware and lighting were on the fire plan review.

Collin was unaware of the deficiencies (painted smoke detectors in the corridor among others) that Jim noted on his inspection. I recommended he contact his fire alarm vendor to walk the site and get any repairs taken care of as well as assess the inadequate coverage in the affected area.

Collin is going to want to set up a conference on site with both of you as well as the building owner and fire alarm vendor to discuss options on not updating the fire alarm in the construction areas. I wanted to give you a heads up so you were both prepared for his request.
FIRE-Final Inspection2/14/20192/14/20192/14/2019PFAIL
DetailsJim Page
Fire alarms in area of work are not code compliant, modifications to the fire alarm system will be required, any modification to the fire alarm system requires a permit. Provide exit lighting as well as emergency lighting per city approved drawings and notes number 15, 16 and 17 of building permit fire code review. Door hardware in area of work needs to comply with note number 5 of building permit fire code review comments. Smoke detectors are required per note number 7 of fire code review, smoke detectors in this building are monitored, a FIR permit will be required for fire alarm modifications. Provide electrical outlet covers per note number 4.

Sadi Phone #: ###-####
(F) Reprint permit  2/14/2019 DONE
Issue PAID IN FULL permit  2/14/2019 DONE
Pending Assignment by CDM1/30/2019 2/13/2019 PASS
DetailsCarl D Madsen
PLANS/APPL TAKEN TO FRONT DESK  2/13/2019 DONE
Case Summary (BLD)  2/13/2019 DONE
Permit Ready to Issue  2/13/2019 DONE
NEED
Letter from parcel owner
GC
Rev cert of val
Print Occupancy Form  2/13/2019 DONE
CHANGE STATUS TO (RDY)  2/13/2019 DONE
was issued by mistake
Print Occupancy Form  2/13/2019 DONE
Telephone call  2/13/2019 DONE
left a message for sadi informing this permit is ready and that the GC will need to turn in the 302 and 306 forms, it will be between them who pays, but the GC will have to sign for the permit
Telephone call  2/13/2019 DONE
spoke with sadi informing her that since no work is being done and just change of use then she is welcome to fill out 302 and 306 forms, but will need to provide a letter from the parcel owner to act as the gc
Routing - FIRE2/11/20192/11/20192/12/2019 PASS
DetailsMark Scharfen
IFC Fire Code Review 02.12.2019 complete.
1st review completed  2/11/2019 DONE
Routing - PLANNING2/8/2019 2/8/2019 PASS
DetailsJeff Lowe
verify at least one bicycle rack installed on-site
Plans ACCEPTED BY PLAN TECH  1/30/2019 DONE
Intake Approval  1/30/2019 PASS
DetailsCarl D Madsen
Recd Pcfee & Taken To Pln CK  1/30/2019 DONE
Application received 1/30/2019