BLD-Final | 6/25/2019 | 6/25/2019 | 6/25/2019 | P | PASS |
Tell Riley
|
|
|
john Phone #: ###-####//final complete per plans//
|
FIRE-Final Inspection | 6/24/2019 | 6/25/2019 | 6/25/2019 | A | PASS |
Jim Page
|
|
|
Previously noted items have been corrected, suite number will be installed before BLD final. Fire sprinkler inspection complete, fire alarm inspection is complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection for area of work complete.
John Phone #: ###-####
|
First Notice | | 7/5/2019 | 6/25/2019 | | DONE |
|
|
|
|
Permanent Occupancy | | | 6/25/2019 | | DONE |
|
|
|
|
FIRE-Final Inspection | 6/24/2019 | 6/24/2019 | 6/24/2019 | P | FAIL |
Jim Page
|
|
|
Emergency lights by east side entry and west side office space did not operate when A/C power was isolated. FIR permit for fire sprinklers needs to be finaled before fire life safety inspection can be completed. Provide suite number for tenant space.
John Phone #: ###-####
|
BLD-Ceiling Grid Inspection | 6/19/2019 | 6/19/2019 | 6/19/2019 | P | PASS |
Tell Riley
|
|
|
John Phone #: ###-####//grid ok per plans//
|
BLD-Framing/Rough-in | 5/24/2019 | 5/24/2019 | 5/24/2019 | A | PASS |
Jim Sly
|
|
|
Call Jon Craft 30 minutes prior. Phone #: ###-#### Inspection requested via web by Jonathan Craft
|
CHANGE STATUS TO (ISS) | | | 5/22/2019 | | DONE |
|
|
|
|
Print Occupancy Form | | | 5/22/2019 | | DONE |
|
|
|
|
Plan assigned to (JG) | 4/26/2019 | 4/26/2019 | 5/21/2019 | | PASS |
Javier Guzman
|
|
|
Plan Mod, Click Funnels - Suite #125
|
Routing - PLAN CHECK | 5/13/2019 | | 5/21/2019 | | PASS |
Javier Guzman
|
|
|
|
Permit Ready to Issue | | | 5/21/2019 | | DONE |
|
|
|
MET EMAIL JTHOMAS@HCCO-INC.COM
Plan Mod Approved
Need-
Revised value for Plan Mod
|
Plan Reviewer's activity | | | 5/7/2019 | | DONE |
Javier Guzman
|
|
|
Prescreen Plan Mod
Provide and show the following:
• Provide top of wall bracing section details
• Provide new suspended acoustic ceiling section details
• With the new conference room, the northern portion of the office is going to require emergency lighting and exit signs. Therefore, provide and show emergency lighting and exist sign locations.
• The new conference room will require receptacle outlets to comply with the 2017 NEC articles 210.71 and 210.52(A)(1)-(A)(4)
(I will email the NEC 2017 code sections so that you may view)
|
Telephone call | | | 4/29/2019 | | DONE |
|
|
|
Spoke with Tucker to confirm this plan mod app is for this permit. That we are still waiting on the signed building permit to be sent back before we can start the plan mod in EPlan. (Sent a reminder to HC COMPANY to please sign the building permit and email it back)
|
Print Occupancy Form | | | 4/26/2019 | | DONE |
|
|
|
|
Issue PAID IN FULL permit | | | 4/26/2019 | | DONE |
|
|
|
|
Plan Modification Accepted | | | 4/26/2019 | | DONE |
|
|
|
plan mod accepted-changes to walls, doors & ceilings no longer to be demolished-sheets G001, AD001 & A112-assigned to JG
|
Route to Impact Fee Review | 3/20/2019 | 3/23/2019 | 3/21/2019 | | PASS |
Shannon Cade
|
|
|
Review requested for Commercial Permit
|
Plan assigned to (JG) | 3/13/2019 | 3/13/2019 | 3/20/2019 | | PASS |
Javier Guzman
|
|
|
3/22 L2 Click Funnels ePlan
|
Routing - PLAN CHECK | 3/13/2019 | | 3/20/2019 | | PASS |
Javier Guzman
|
|
|
|
1st review completed | | | 3/20/2019 | | DONE |
Javier Guzman
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/20/2019 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 3/20/2019 | | DONE |
|
|
|
MET
Need GC
Need rev cert of val
|
Routing - Addressing | 3/13/2019 | | 3/13/2019 | | PASS |
Doug Chausow
|
|
|
Suite 125
|
Routing - PUBLIC WORKS | 3/13/2019 | | 3/13/2019 | | PASS |
Angela Hardy
|
|
|
|
Intake Approval | | | 3/11/2019 | | PASS |
Javier Guzman
|
|
|
|
Intake Approval | | | 3/6/2019 | | FAIL |
Michael Hanson
|
|
|
This permit has failed prescreen due to the following:
1. Provide FE location for this space
2. Provide lighting information.
3. Provide door hardware information.
|
Application received | | | 3/4/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Mar 4 2019 4:14PM
|