First Notice | | 1/23/2020 | 1/23/2020 | | DONE |
|
|
|
This permit final value done with ELE19-03727.
|
First Notice | 10/7/2019 | 10/7/2019 | 10/7/2019 | | DONE |
Rock A. Hudson
|
|
|
This permit finaled on the web by Debby Pierce
|
Final | 10/3/2019 | 10/7/2019 | 10/7/2019 | A | PASS |
Rock A. Hudson
|
|
|
Geoff Hannaford is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce Final ok
|
Final | 9/30/2019 | 10/1/2019 | 10/1/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Geoff Hannaford is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce 110.26(D)- Illumination shall be provided for all work spaces about panel boards. Vanilla spaces need illumination for panels. *ELE18-04645 is attached to BLD18-01882 shell permit. Informed on 12-11-18 that seperate permit needed for other BLD18-03045. No action taken as of 10-1-19. Unable to final until proper permits in place.
|
Electrical Rough-In | 8/7/2019 | 8/8/2019 | 8/8/2019 | A | CANC |
Daryl DeGrange
|
|
|
Geoff Hannaford is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce Contractor needed permanent service rather than rough-in
|
Permanent Service | 8/8/2019 | 8/8/2019 | 8/8/2019 | A | PASS |
Daryl DeGrange
|
|
|
Geoff Hannaford is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce P/S U/G N OK
|
Electrical Rough-In | 7/9/2019 | 7/10/2019 | 7/10/2019 | A | PASS |
Eric Story
|
|
|
Geoff Hannaford is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce Walls and hard lids ok to cover
|
Electrical Rough-In | 5/3/2019 | 5/6/2019 | 5/6/2019 | A | PASS |
Rock A. Hudson
|
|
|
Geoff Hannaford is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce Under slab rough in ok cover.
|
Electrical Rough-In | 1/8/2019 | 1/9/2019 | 1/9/2019 | A | PASS |
Rock A. Hudson
|
|
|
underground, Phone #: ###-#### Inspection requested via web by Debby Pierce Permit has been changed to the core and shell building permit. Underground on south side run along foundation rough in ok cover
|
Fees Due Hold | 12/12/2018 | | 12/12/2018 | | DONE |
|
|
|
|
Electrical Rough-In | 12/11/2018 | 12/11/2018 | 12/11/2018 | P | FAIL |
Rock A. Hudson
|
|
|
For ufer ground, contact Ken Williams at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce Permit is for TI portion of job, new electrical permit is required for core and shell of building to be attached to BLD18-01882. Concrete encased electrode covered prior to inspection. Still required to use it as part of grounding electrode system with building steel and any underground metal water pipes present. Will make noted of concrete encased electrode when new electrical permit exists for shell portion on job.
|
Telephone call | | | 12/11/2018 | | DONE |
|
|
|
per Debbie needed to add 6500 to value and attach to the core and shell. will pull permit for the ti when ready
|
Issue PAID IN FULL permit | | | 12/5/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 12/5/2018 | | |
|
|
|
|
Application received | | | 12/5/2018 | | DONE |
|
|
|
This permit was created on the web by Debby Pierce
|