Final | 4/10/2019 | 4/10/2019 | 4/10/2019 | P | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Garrett Collins Ok final.
|
Final | 4/8/2019 | 4/9/2019 | 4/9/2019 | P | NR |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Garrett Collins
|
Electrical Rough-In | 1/10/2019 | 1/11/2019 | 1/11/2019 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Garrett Collins Rough in ok cover
|
Electrical Rough-In | 1/9/2019 | 1/10/2019 | 1/10/2019 | P | FAIL |
Rock A. Hudson
|
|
|
Elec ri. Zach on site. Phone #: ###-#### Inspection requested via web by Garrett Collins 210.52- A receptacle outlet shall be installed with in 6' of pocket door in master bedroom. 300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from damage by nail plates in kitchen near sink. 314.17(C)- Where knob and tube wiring enter a non-metallic box the conductors shall enter thru individual holes. Kitchen ceiling near door. 334.30- NM calbe shall be secured in place with in 12" of a box. NM cable passes thru hole in beam and enters recessed can with out being secured in place. House is unoccupied
|
Issue PAID IN FULL permit | | | 1/2/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/2/2019 | | DONE |
|
|
|
This permit was created on the web by Garrett Collins
|