Final | 2/5/2020 | 2/6/2020 | 2/6/2020 | A | PASS |
Mark Moncarr
|
|
|
lockbox 1319. Powder bath outlet is connected to GFCI in master bath and was tripped. Tile heat stat has been moved to allow access. Extension box on island. Phone #: ###-#### Inspection requested via web by Heath Thomas Ok final. Corrections made.
|
Final | 1/31/2020 | 2/3/2020 | 2/3/2020 | A | FAIL |
Rock A. Hudson
|
|
|
lockbox 1319 Phone #: ###-#### Inspection requested via web by Heath Thomas 110.3- Poder bath receptacles not working. Master bath floor heat thermostat too close to wall cannot reset GFCI in right side. 314.16- Receptacle installed for kitchen island counter top shall be of sufficient size for conductor allowance installed. 11.25 cubic inches installed in a 8 cubic inch box.
|
Electrical Rough-In | 12/27/2019 | 12/27/2019 | 12/27/2019 | P | PASS |
Eric Story
|
|
|
Floor heat in master bathroom. Lockbox code on front door is 2520. Key is for dead bolt lock. Phone #: ###-#### Inspection requested via web by Heath Thomas Master floor heat ok to cover
|
Rough-In Permanent Service | 10/17/2019 | 10/18/2019 | 10/18/2019 | A | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Heath Thomas Corrections made. Ok cover. p/s u/g n ok
|
Rough-In Permanent Service | 10/16/2019 | 10/17/2019 | 10/17/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Heath Thomas 314.25- Recess can junction box covers shall be installed to totally enclose box as per manufacturers instructions. Master hall can, master bed can, kitchen can back junction box covers not flush with box. * Complete dry sheeting ASAP! It is raining at time of inspection.
|
Issue PAID IN FULL permit | | | 9/30/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/30/2019 | | DONE |
|
|
|
This permit was created on the web by Heath Thomas
|