INSP-Final Inspection | 10/16/2019 | 10/17/2019 | 10/17/2019 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled.
Contact is Morgan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
Plan Modification Accepted | | | 10/15/2019 | | DONE |
|
|
|
as built per morgan with protex
|
Plan assigned to (Lee) | 10/15/2019 | | 10/15/2019 | | DONE |
Lee G Meredith
|
|
|
|
Intake Approval | | | 10/15/2019 | | PASS |
|
|
|
|
1st review completed | | | 10/15/2019 | | PASS |
|
|
|
|
Alarm Plan Check | 10/15/2019 | | 10/15/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 10/15/2019 | | DONE |
|
|
|
As built - No fee.
|
Permit Ready to Issue | | | 10/15/2019 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 10/15/2019 | | DONE |
|
|
|
as built
|
INSP-Final Inspection | 10/14/2019 | 10/14/2019 | 10/14/2019 | P | FAIL |
Troy Cobbley
|
|
|
Need as-builts showing the candella change and the added duct smoke detector. Contact is Dirk. Client requests final for after school hours. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
Plan assigned to (Lee) | 10/3/2019 | | 10/10/2019 | | DONE |
Lee G Meredith
|
|
|
|
Intake Approval | | | 10/10/2019 | | PASS |
|
|
|
|
1st review completed | | | 10/10/2019 | | PASS |
|
|
|
|
Alarm Plan Check | 10/10/2019 | | 10/10/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 10/10/2019 | | DONE |
|
|
|
As built - No fee.
|
Permit Ready to Issue | | | 10/10/2019 | | DONE |
|
|
|
As built approved
|
CHANGE STATUS TO (ISS) | | | 10/10/2019 | | DONE |
|
|
|
|
INSP-Final Inspection | 10/2/2019 | 10/3/2019 | 10/3/2019 | P | FAIL |
Troy Cobbley
|
|
|
Ceiling mounted strobes are overspaced in the Kitchen. Inspection stopped. Devices need to be relocated or candellas adjusted. The fire alam plans need to be reviewed by the engineer of record prior to plan review approval. Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
Plan resubmittals received | | | 10/3/2019 | | DONE |
|
|
|
Morgan with Protex required for the workflow to be opened for as builts
|
Application received | | | 6/17/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Jun 17 2019 11:57AM
|
Plan assigned to (Lee) | 6/17/2019 | | 6/17/2019 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 6/17/2019 | | PASS |
|
|
|
|
Alarm Plan Check | 6/17/2019 | | 6/17/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 6/17/2019 | | DONE |
|
|
|
Passed with review comments and drawing notes.
|
Permit Ready to Issue | | | 6/17/2019 | | DONE |
|
|
|
|
Issue and Print Permit | | | 6/17/2019 | | DONE |
|
|
|
|