Final | 4/12/2019 | 4/12/2019 | 4/12/2019 | P | PASS |
Brian Scoles
|
|
|
approved man J now on site and balance report was in lit rack in furnace closet. Re inspection code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- HVAC and fireplace final ok
|
Final | 4/8/2019 | 4/11/2019 | 4/11/2019 | A | FAIL |
Brian Scoles
|
|
|
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- need approved man j and air balance report onsite none could be found
|
Rough-in | 2/26/2019 | 2/27/2019 | 2/27/2019 | P | PASS |
Brian Scoles
|
|
|
re inspection 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- R/
I ok
|
Rough-in | 2/25/2019 | 2/26/2019 | 2/26/2019 | P | FAIL |
Brian Scoles
|
|
|
re inspection code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- all corrections not made- need to insulate wye branch front entry door bare metal showing- water heater b vent needs 1" clearance to plywood where b vent goes thru 1st floor ceiling in chase from garage- correction notice still posted front entry window
|
Pressure Test | 2/25/2019 | 2/26/2019 | 2/26/2019 | P | PASS |
Brian Scoles
|
|
|
re inspection code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- 20lb gas pass- tagged meter location-
|
Rough-in | 2/19/2019 | 2/25/2019 | 2/25/2019 | A | FAIL |
Brian Scoles
|
|
|
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- 1) need approved manual j onsite no prints could be found 2) water heater flue needs 1" clearance to combustibles in garage at ceiling 3) all R/A and supply boots need sealed 4) fireplace thimble inside exterior wall upside down doesnt meet clearance per installation instructions 5) outside air can needs insulated and sealed in attic where ties onto R/A plenum 6)R/A ducting off top of plenum needs to be secured father away from b vent in attic 7)supply wye branches need insulated in a couple places in attic bare metal showing 8) gas test failed gauge wont zero out-
left correction notice front entry window
|
Pressure Test | 2/19/2019 | 2/25/2019 | 2/25/2019 | A | FAIL |
Brian Scoles
|
|
|
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- gauge wont zero out
|
Issue PAID IN FULL permit | | | 2/19/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/19/2019 | | DONE |
|
|
|
This permit was created on the web by Randy Hart
|