Final | 1/2/2020 | 1/3/2020 | 1/3/2020 | A | PASS |
Jack Reynolds
|
|
|
Final Inspection - T ; B provided Phone #: ###-#### Inspection requested via web by Beka Hereau - final ok - occ card signed
|
Final | 11/7/2019 | 11/8/2019 | 11/8/2019 | A | PART |
Jack Reynolds
|
|
|
Temp Final for temp c of o Phone #: ###-#### Inspection requested via web by Beka Hereau - partial final ok - need to see balance report for final - signed temp occ card
|
Rough-in | 11/5/2019 | 11/5/2019 | 11/5/2019 | P | PASS |
Jack Reynolds
|
|
|
Rough In for cover Phone #: ###-#### Inspection requested via web by Beka Hereau - R/I ceiling cover ok
|
Rough-in | 10/25/2019 | 10/28/2019 | 10/28/2019 | P | PART |
Jack Reynolds
|
|
|
FIRE Damper Rough In - Inspection Phone #: ###-#### Inspection requested via web by Beka Hereau - fire damper clearances ok -all fire caulk needs to be removed and fire damper access doors installed by ceiling R/I cover - radiant heater flue clearnaces ok need to caulk all exhaust venting seams
|
Rough-in | 10/23/2019 | 10/24/2019 | 10/24/2019 | A | FAIL |
Jack Reynolds
|
|
|
Rough In Inspection of Dampers - someone will be on site Phone #: ###-#### Inspection requested via web by Beka Hereau - duct work ok - still need proper installation instructions for round fire dampers. All angles need removed to check clearances. remove fire caulk on dampers unless instructions say to do so. Each fire damper will also need an access door installed. - condensates for units ok - exhaust side of radiant heaters needs sealed with high temp sealer and need to check clearances on vent throughn roof
|
Rough-in | 10/17/2019 | 10/18/2019 | 10/18/2019 | A | FAIL |
Jack Reynolds
|
|
|
Rough In Inspection Phone #: ###-#### Inspection requested via web by Beka Hereau - no access to location - talking with Rich retaining angles on fire dampers will need to be removed and installation instructions be onsite for next inspection. - Re schedule R/I inspection and fire damper inspection
|
Issue PAID IN FULL permit | | | 9/26/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/26/2019 | | DONE |
|
|
|
This permit was created on the web by Beka Hereau
|
First Notice | 1/3/2020 | 1/3/2020 | | | |
Jack Reynolds
|
|
|
|