Permit Information
Permit NumberBLD17-04134
StatusFinaled
Name NOLIND AND CREW INC
Site Address 710 N ORCHARD ST
Project NameFood Land Market
Customer Number 
ePlanReviewYes
Description
(FOOD LAND MARKET – RETAIL SALES AND DINING – NORTH HALF OF BUILDING) This building does not have a fire sprinkler system. To remodel an existing 4,100 square foot tenant space located within an existing 9,300 square foot, one story building for a new retail sales and dining tenant. A full commercial kitchen will be created. Work is to include a new interior door opening in an existing masonry wall, a steel header and trimmers at that new masonry wall opening, a 3-hr party wall door infill, an interior nonbearing wall, interior noncombustible furred walls at grease hoods, two Class I grease hoods (542 pounds each), fire duct wrap for reduced clearances to combustibles, a 453 pound Class II hood, a 1,437 pound roof top make-up air unit, kitchen equipment, reach in coolers, shelving units for sales, sales counters, display units, millwork, and finishes. The accessible toilet room is required to be upgraded to be accessible to the disabled as defined by current standards. A separate permit is required for shelves more than 8 feet in height. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final4/16/20194/17/20194/17/2019APASS
DetailsJim Sly
Jake- please give call 20 min prior, he is not available between 11-12. Phone #: ###-####
OK for Temp. Occ. OK for Perm. Occ. when........Plumbing signs off Perm, and Locksets on office and storage room doors are changed out. (3). 5-14-19-as per Jim Sly ok to change PART to Final
BLD-Final4/15/20194/16/20194/16/2019ANH
DetailsJim Sly
Jake-call 20 minutes prior to meet Phone #: ###-####
Called twice.....Busy signal.......left Note on door. No access........
FIRE-Final Inspection4/15/20194/15/20194/15/2019PPASS
DetailsTroy Cobbley
Life safety passed. Contractor to provide single action hardware on the Office door, door that isolates Storage area and the exterior exit door from the Storage area prior to a building inspection as per discussion.


after 130....please call 20 mins before // jake Phone #: ###-####
FIRE-Final Inspection2/13/20192/14/20192/14/2019AFAIL
DetailsTroy Cobbley
Provide review comments, provide exit discharge lights at the two exits, the pizza oven must fit under the hood by 6" as per mechanical code, provide single action (lever type) hardware for doors 103A and 102A, remove both dead bolts at the main exit doors, provide panic hardware and exit light, exit sign, exit discharge light at door 106A or provide plan review approval of alternate (plans show area as a "M" but is currently being used as an "S").

Jake-please call 20 minutes prior to meet for access Phone #: ###-####
BLD-Ceiling Grid Inspection1/10/20191/11/20191/11/2019PPASS
DetailsJim Sly
Jake-pleae call 20 minutes prior to meet Phone #: ###-####
BLD-Ceiling Grid Inspection7/16/20187/17/20187/17/2018ANR
DetailsDave Hannah
Jake-please call 30 mintues prior to meet Phone #: ###-####
BLD-Framing/Rough-in4/25/20184/25/20184/26/2018PPART
DetailsJim Sly
Jake Phone #: ###-####
Select walls