Information based on query as of Thursday, June 6, 2024.
Permit Information
Permit NumberBLD18-00945
StatusIssued
Name PERKINS CONSTRUCTION
Site Address 3722 W ANDERSON ST
Project NameTaft Elementary Addition
Customer Number 
ePlanReviewYes
Description
**(TAFT ELEMENTARY – GYMNASIUM) // 09-13-18 PLAN MODIFICATION TO RELOCATE THE SANITARY SEWER SERVICE CONNECTION. JAR // **This building is NOT fire sprinklered. Permit to construct a new 5,749 square foot gymnasium and 732 sq ft pedestrian walkway with associated support areas including restrooms, office, storage, and mechanical rooms as well as remodel of kitchen in existing classroom building on the Taft Elementary School campus. Work also includes general site work. Special inspections required per attached Form 310. All work per the approved plans and notations. This building is fully alarmed. **JAR**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final1/9/20201/9/20201/9/2020PNR
DetailsTony Young
Phone #: ###-#### Inspection requested via web by Ron Goff// need letters from the engineer
BLD-Final1/8/20201/8/20201/8/2020PCANC
DetailsTony Young
ron Phone #: ###-#### Inspection cancelled from web by: Ron Goff
BLD-Aging Inspection9/25/20199/25/20199/27/2019 PEND
DetailsTony Young
BLD-Aging Inspection9/24/20199/24/20199/27/2019 PEND
DetailsTony Young
BLD-Final5/13/20195/13/20195/13/2019PPART
DetailsTony Young
Ron Phone #: ###-####,, needs final letter from engineer,, all structural elements.. also final inspections from CDHD and zoning.. temp accupancy to move things in ok ((spoke with Tony on the phone 5-20-19 CDHD, PW, and Zoning inspections all require a Partial Final to get a Temps CO)) J.A.
FIRE-Final Inspection5/7/20195/8/20195/8/2019APASS
DetailsTroy Cobbley
Previous corrections addressed. Life safety passed. Ron Phone #: ###-####
FIRE-Final Inspection4/19/20194/22/20194/22/2019AFAIL
DetailsJim Page
Provide city approved drawings showing the exit/egress lighting plan, none provided, sheets were missing in approved drawing packet. Provide small documents. Install knox box as discussed. Install FACP signage on fire alamr panel room.

alarm Gym // Ron Phone #: ###-####
FIRE-Final Inspection3/15/20193/15/20193/15/2019PPART
DetailsJim Page
Fire alarm and hood suppression system inspection for kitchen area have been completed, fire extinguishers are placed with current inspection tags. Life fire safety inspection for kitchen TCO complete.

Ron-kitchen area Phone #: ###-####
FIRE-Final Inspection3/1/20193/4/20193/4/2019AFAIL
DetailsJim Page
As stated before, no fire alarm inspection has been requested nor finaled for area of work, fire life safety inspection will not be performed or completed until fire alarms are inspected and passed, during hood inspection is was noticed that the fire alarm system has 3 different tones in the gym area when fire alarm is activated, this is not code compliant.

Ronald-partial life safety kitchen only Phone #: ###-####
BLD-Final2/28/20193/1/20193/1/2019PNR
DetailsTony Young
Ronald Phone #: ###-####,, needs trades 1st,, needs letter from engineer that all is good,, not many inspections were called in,, called ,, no answer,, left messege
FIRE-Final Inspection2/28/20193/1/20193/1/2019AFAIL
DetailsJim Page
Fire alarm permit (FIR18-00644) associated with this project has not been inspected or finaled, fire alarm inspection needs to be completed and finaled before life fire safety inspection can be perfromed.ron Phone #: ###-####
BLD-Aging Inspection11/28/201811/28/201812/3/2018 PEND
DetailsTony Young
BLD-Aging Inspection11/27/201811/27/201812/3/2018 PASS
DetailsTony Young
BLD-Ceiling Grid Inspection11/5/201811/5/201811/5/2018PPASS
DetailsTony Young
Ron Phone #: ###-####
BLD-Foundation8/3/20188/6/20188/6/2018APEND
DetailsTony Young
Ron Phone #: ###-####,, pending special inspection
BLD-Foundation8/2/20188/3/20188/3/2018PPEND
DetailsTony Young
Ron Phone #: ###-####
BLD-Footing7/11/20187/16/20187/16/2018APART
DetailsTony Young
Ron Phone #: ###-####,, pending special inspection report
BLD-Footing7/5/20187/11/20187/11/2018APART
DetailsMike Jordan
(request 11am) Ron Phone #: ###-####. perimeter footings. Needs to add verts and corners and intersections. Concrete placement cancelled due to no special inspection.