Permit Information
Permit NumberBLD18-02797
StatusFinaled
Name STEED CONSTRUCTION
Site Address 601 W GOWEN RD
Project NameWestern Power Sports Addition
Customer NumberESC18-00979/BLD18-03305
ePlanReviewYes
Description
(WESTERN POWER SPORTS) (Project Management - Ron Hill) Grading & Utilities issued (GRD18-00053) Permit for the addition of 105,518 s.f. of new warehouse space to the existing Western Power Sports warehouse located at 601 W. Gowen Rd with work to include the construction of a concrete tilt-up building associated fire riser/pump room and associated site work per the approved plans. A separate racking permit is required. This building is fully fire sprinklered for unlimited area with 60 foot yards. Any alterations to the sprinkler system will require a separate permit and shall comply with NFPA 13 as regulated by the fire department. CDM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final10/17/201910/18/201910/18/2019APASS
DetailsJim Storey
Mike Phone #: ###-####
FIRE-Final Inspection8/14/20198/15/20198/15/2019APASS
DetailsJim Page
Previously noted items have been completed, final life fire safety inspection complete.

Mike Phone #: ###-####
BLD-Final7/18/20197/19/20197/19/2019PNR
DetailsJim Storey
mIKE Phone #: ###-#### ok to stock racking per fire tco
FIRE-Final Inspection7/18/20197/19/20197/19/2019APART
DetailsJim Page
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are placed with current inspection tags. Partial final inspection complete for life fire safety, last remaining items to be completed before final life fire safety sign off is provide FACP signage on door leading to fire panel, install fire lane signage as specified in review comments under notes 9 and 10 of the building permit fire code review comments. Need to verify if old fire pump room is staying in place ot being removed, if existing pump room stays then fire sprinklers will need to be provided. 30 day TCO authorized per conversation with Ron Johnson with Boise Fire contingent on the 3 noted items getting completed.

mIKE Phone #: ###-####
FIRE-Final Inspection7/15/20197/16/20197/16/2019PCANC
DetailsJim Page
Cancelled per conversation with point of contact, fire alarm inspection has been cooridanted with me, Apex and any parties associated with access to the existing building for 7AM on 19JULY2019.
Mike Phone #: ###-####
BLD-Final7/16/20197/16/20197/16/2019PCANC
DetailsJim Storey
FIRE-Final Inspection7/14/20197/15/20197/15/2019AFAIL
DetailsJim Page
Relocate exit signs that are blocked due to racking placement. Fire hydrants need to be rotated so that the large hose connection (Steamer Connection) is pointing at the fire lane as required.

Jim Wellman Phone #: ###-#### Inspection requested via web by Jim Wellman
BLD-Final7/14/20197/15/20197/15/2019ANR
DetailsJim Storey
Jim Wellman Phone #: ###-#### Inspection requested via web by Jim Wellman
FIRE-Conference7/2/20197/3/20197/3/2019ADONE
DetailsJim Page
Fire conference is complete, items that are not associated with construction are not to be stored in the warehouse. As of this entry the racking permit has not been inspected, the fire alarms cannot be completed due to the fire alarm permit being under review and no life fire safety inspection has been performed. I spoke with Ron Johnson with Boise Fire Department and he agrees with my decision.

call ahead // Mike Phone #: ###-####
FIRE-Conference6/25/20196/26/20196/26/2019ADONE
DetailsJim Page
Fire conference complete, per international fire code, section 1013.1 requires exit signs to be visible within 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.

Mike Phone #: ###-####
BLD-Conference6/4/20196/5/20196/5/2019PDONE
DetailsJim Page
Fire conference complete.

Mike-Conference with Fire inspector- please call about an hor before Phone #: ###-####
BLD-Framing/Rough-in5/7/20195/8/20195/8/2019PPASS
DetailsJim Storey
Mike Phone #: ###-#### fire pump rm ok to cover
BLD-Ceiling Grid Inspection4/18/20194/18/20194/18/2019PPASS
DetailsJim Storey
Mike Phone #: ###-####
BLD-Ceiling Grid Inspection4/12/20194/15/20194/15/2019APASS
DetailsJim Storey
Mike Phone #: ###-####
BLD-Ceiling Grid Inspection4/9/20194/10/20194/10/2019APASS
DetailsJim Storey
Mike Phone #: ###-####
BLD-Ceiling Grid Inspection4/8/20194/9/20194/9/2019ACANC
DetailsMike Jordan
Mike Phone #: ###-####
BLD-Ceiling Grid Inspection4/4/20194/5/20194/5/2019APART
DetailsJim Storey
Mike Phone #: ###-#### east side ok
BLD-Ceiling Grid Inspection3/25/20193/25/20193/25/2019PPART
DetailsJim Storey
Mike Phone #: ###-#### ok to instal tile as progressing across ceilling.
FIRE-Conference3/19/20193/19/20193/19/2019ADONE
DetailsJim Page
General contractor has been notified as of this date that fire hydrants around project need to be made active during construction.