BLD-Final | 2/22/2019 | 2/22/2019 | 2/22/2019 | P | PASS |
Tony Young
|
|
|
Anthony Phone #: ###-####
|
FIRE-Final Inspection | 2/21/2019 | 2/21/2019 | 2/21/2019 | P | PASS |
Jim Page
|
|
|
Previously noted items have been corrected, final life fire safety inspection complete.
Anthony Phone #: ###-####
|
FIRE-Final Inspection | 2/20/2019 | 2/20/2019 | 2/20/2019 | P | FAIL |
Jim Page
|
|
|
Provide exit signage and emergency lighting on the southside enclosed patio. Provide emergency lighting in corridor between restrooms. Provide signage over the top of the main entry reading "Door to remain unlocked while building is occupied". South door swings the wrong direction for path of travel, need to correct door swing and install panic type door hardware per building fire code review comments. Place fire extinguishers in discussed locations.
Anthony Phone #: ###-####
|
BLD-Framing/Rough-in | 2/5/2019 | 2/6/2019 | 2/6/2019 | A | PASS |
Tony Young
|
|
|
Anthony Phone #: ###-####,, exterior corner frame ok
|
BLD-Framing/Rough-in | 1/29/2019 | 1/30/2019 | 1/30/2019 | A | PART |
Tony Young
|
|
|
Antonio Phone #: ###-####,, rest room walls ok to cover,, all interior walls ok
|