Description
**(IMPACT GROUP)** Application for inspection to determine requirements for issuance of a Certificate of Occupancy for a 8,368 sq. ft. existing office building (5,100 sq. ft. 1st floor + 3,268 sq. ft. 2nd floor) previously occupied by “VIQ Development” under BLD13-01956 and “Wellness Chiropractic” under BLD13-02086 . NO NEW WORK IS AUTHORIZED UNDER THIS PERMIT. There will be no change to the occupancy. This building is Not fire sprinklered. **JG**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final1/4/20191/7/20191/7/2019PPASS
DetailsDave Hannah
Rebecca Phone #: ###-####
FIRE-Final Inspection1/3/20191/4/20191/4/2019APASS
DetailsJim Page
Previously noted items have been corrected, final life fire safety inspection complete.

Rebecca Phone #: ###-####
BLD-Final12/10/201812/11/201812/11/2018PCANC
DetailsBrandon Shaw
Need Fire final...
FIRE-Final Inspection12/10/201812/11/201812/11/2018AFAIL
DetailsJim Page
Fire extinguishers need to be inspected and tagged accordingly. Mount fire extinguishers as discussed, maximum of 75 foot walking distance for each extinguisher as per code. Service or replace exit signs that are inoperable. Provide signage on main entry doors reading "Door to remain unlocked while building is occupied".

Rebecca Phone #: 208-###-####-please call a few minutes prior to meet for access