Permit Information
Permit NumberBLD18-04417
StatusFinaled
Name LETICIA MCLAUGHLIN
Site Address 1555 S BROADWAY AVE
Project NameJalapenos Bar & Grill
Customer Number 
ePlanReviewNo
Description
(JALAPENOS BAR & GRILL) Application for inspection to determine the requirements for the issuance of a Certificate of Occupancy for an existing 8,555 square foot restaurant building to be used by a new restaurant tenant. Certificate of Occupancy was previously issued under Tap and Cask BLD17-00027 & Tilted Kilt Pub BLD13-03353. No new work is authorized under this permit. Painting, carpeting, counter tops, shelves, and similar finish work are not required to have a building permit. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **JHB**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final1/11/20191/14/20191/14/2019APASS
DetailsJim Storey
Leticia Phone #: ###-####
FIRE-Final Inspection1/11/20191/11/20191/11/2019PPASS
DetailsTroy Cobbley
Life safety passed. The fire alarm panel is clear of troubles


Leticia Phone #: ###-####
FIRE-Final Inspection12/28/201812/28/201812/28/2018PPART
DetailsJim Page
Previously noted items for life fire safety inspection have been completed. Phone lines for fire panel monitoring were effected by Century Link failure so fire panel was showing a communication failure, per conversation with Ron Johnson a fire watch is recommended and a 15 day TCO is authorized contingent on phone lines being repaired and fire sprinkler monitoring is established.
BLD-Final12/26/201812/26/201812/26/2018PPART
DetailsJim Storey
call 10 mins ahead- Leticia Phone #: ###-#### remove dead bolt at fireriser rm/ storage rm door hardware or remove. pending fire sign off.
FIRE-Final Inspection12/26/201812/26/201812/26/2018PCANC
DetailsJim Page
Cancelled per conversation with point of contact, an FIR permit is required for hood suppression system modifications.

call 10 mins ahead- Leticia Phone #: ###-####
BLD-Final12/20/201812/21/201812/21/2018PNR
DetailsJim Storey
Leticia Phone #: ###-####
FIRE-Final Inspection12/20/201812/21/201812/21/2018AFAIL
DetailsJim Page
Fire spribkler head next to center bar area has head within 12 inches of air diffuser, needs to be an intermediate temperature head to be code compliant, current temp for sprinkler is 155 degree. Numerous escutcheons are missing throughout, all escutcheons need to be in place on fire sprinklers. New cooking epuipment has been installed as well as exisitng cooking equipment has been moved, modification to the hood fire suppression system may be required, contact a licensed commercial hood contractor for corrections (A permit will be required for ANY modifications to the hood system).

Leticia Phone #: ###-####
FIRE-Final Inspection12/14/201812/14/201812/14/2018PFAIL
DetailsJim Page
Attempted to call point of contact with phone number that was provided at 2:53PM, left a voicemail with my contact information, waited until 4PM with no call back. Inspection will need to be rescheduled.

Leticia Phone #: ###-####