BLD-Final | 1/11/2019 | 1/14/2019 | 1/14/2019 | A | PASS |
Jim Storey
|
|
|
Leticia Phone #: ###-####
|
FIRE-Final Inspection | 1/11/2019 | 1/11/2019 | 1/11/2019 | P | PASS |
Troy Cobbley
|
|
|
Life safety passed. The fire alarm panel is clear of troubles
Leticia Phone #: ###-####
|
FIRE-Final Inspection | 12/28/2018 | 12/28/2018 | 12/28/2018 | P | PART |
Jim Page
|
|
|
Previously noted items for life fire safety inspection have been completed. Phone lines for fire panel monitoring were effected by Century Link failure so fire panel was showing a communication failure, per conversation with Ron Johnson a fire watch is recommended and a 15 day TCO is authorized contingent on phone lines being repaired and fire sprinkler monitoring is established.
|
BLD-Final | 12/26/2018 | 12/26/2018 | 12/26/2018 | P | PART |
Jim Storey
|
|
|
call 10 mins ahead- Leticia Phone #: ###-#### remove dead bolt at fireriser rm/ storage rm door hardware or remove. pending fire sign off.
|
FIRE-Final Inspection | 12/26/2018 | 12/26/2018 | 12/26/2018 | P | CANC |
Jim Page
|
|
|
Cancelled per conversation with point of contact, an FIR permit is required for hood suppression system modifications.
call 10 mins ahead- Leticia Phone #: ###-####
|
BLD-Final | 12/20/2018 | 12/21/2018 | 12/21/2018 | P | NR |
Jim Storey
|
|
|
Leticia Phone #: ###-####
|
FIRE-Final Inspection | 12/20/2018 | 12/21/2018 | 12/21/2018 | A | FAIL |
Jim Page
|
|
|
Fire spribkler head next to center bar area has head within 12 inches of air diffuser, needs to be an intermediate temperature head to be code compliant, current temp for sprinkler is 155 degree. Numerous escutcheons are missing throughout, all escutcheons need to be in place on fire sprinklers. New cooking epuipment has been installed as well as exisitng cooking equipment has been moved, modification to the hood fire suppression system may be required, contact a licensed commercial hood contractor for corrections (A permit will be required for ANY modifications to the hood system).
Leticia Phone #: ###-####
|
FIRE-Final Inspection | 12/14/2018 | 12/14/2018 | 12/14/2018 | P | FAIL |
Jim Page
|
|
|
Attempted to call point of contact with phone number that was provided at 2:53PM, left a voicemail with my contact information, waited until 4PM with no call back. Inspection will need to be rescheduled.
Leticia Phone #: ###-####
|