Permit Information
Permit NumberBLD19-00582
StatusFinaled
Name NICK COFOD
Site Address 601 S 9TH ST
Project NameFoothills School of Arts & Sci
Customer Number 
ePlanReviewNo
Description
**(FOOTHILLS SCHOOL OF ARTS AND SCIENCES)** Application for inspection to determine requirements for issuance of a Certificate of Occupancy for a 22,046 sq. ft. existing Educational and Business tenant. This space was previously occupied by "Sage Charter School" under BLD12-01557. NO NEW WORK IS AUTHORIZED UNDER THIS PERMIT. There will be no change to the occupancy. **BJM**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final3/29/20194/1/20194/1/2019APASS
DetailsDave Hannah
Tina-(works with Nick) Phone #: ###-####
FIRE-Final Inspection3/29/20194/1/20194/1/2019APASS
DetailsJim Page
Fire sprinkler modifications completye (FIR19-00177), no fire alarm modifications, fire extinguishers are placed with current inspection tags, emergency lighting has been repaired since previous comments. Final life fire safety inspection complete.

830 // tina Phone #: ###-####
FIRE-Final Inspection3/29/20193/29/20193/29/2019PCANC
DetailsJim Page
Spoke with point of contact, life fire safety inspection will be rescheduled to coincide with fire sprinkler inspection. This request is cancelled.

Tina-(works with Nick) Phone #: ###-####
BLD-Final3/1/20193/4/20193/4/2019ACANC
DetailsDave Hannah
call ahead // Tina Phone #: ###-####
FIRE-Final Inspection3/1/20193/1/20193/1/2019PFAIL
DetailsJim Page
Service or replace exit signs and emergency lighting that is inoperable as discussed. Provide annual inspections for fire extinguishers, last inspection for extinguishers was 2016. Fire sprinkler system has a current inspection tag. Preaction fire sprinkler system riser is still in place but has been disconnected and removed from service, fire sprinkler piping on the preaction system has been converted to a wet system but valve trim is still in place. Change pendant fire sprinkler that is to close to wall to a vertical sidewall to be code compliant.

call ahead // Nick Phone #: ###-####