Description
(SYSTEM ONE HOLDINGS – COLUMBIA BUILDING - SUITE #125) //Plan modification to remove select demo work from scope of work, adding half height walls, create a new conference room, select new suspended acoustic ceiling and electrical work. 5-21-2019 JG// Permit is to combine an existing 3,088 sq. ft. business space with the adjacent 4,117 sq. ft. vanilla space on the north end of the building (vanilla created under BLD18-03324) to create a new office tenant space that is 7,211 sq. ft. within the existing building. Approval is contingent upon adhering to the approved plans on file. Work to include: removal of select door/door frame, removal of select interior nonbearing walls, removal of select ceiling, select construction of wall infill and add new interior window, millwork, select new suspended acoustic ceiling, electrical work and interior finishes in compliance with Ch. 8 of the current IBC. This building is fully Fire Sprinklered. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **JG**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final6/25/20196/25/20196/25/2019PPASS
DetailsTell Riley
john Phone #: ###-####//final complete per plans//
FIRE-Final Inspection6/24/20196/25/20196/25/2019APASS
DetailsJim Page
Previously noted items have been corrected, suite number will be installed before BLD final. Fire sprinkler inspection complete, fire alarm inspection is complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection for area of work complete.

John Phone #: ###-####
FIRE-Final Inspection6/24/20196/24/20196/24/2019PFAIL
DetailsJim Page
Emergency lights by east side entry and west side office space did not operate when A/C power was isolated. FIR permit for fire sprinklers needs to be finaled before fire life safety inspection can be completed. Provide suite number for tenant space.

John Phone #: ###-####
BLD-Ceiling Grid Inspection6/19/20196/19/20196/19/2019PPASS
DetailsTell Riley
John Phone #: ###-####//grid ok per plans//
BLD-Framing/Rough-in5/24/20195/24/20195/24/2019APASS
DetailsJim Sly
Call Jon Craft 30 minutes prior. Phone #: ###-#### Inspection requested via web by Jonathan Craft