BLD-Final | 3/11/2020 | 3/12/2020 | 3/12/2020 | A | PASS |
Dave Hannah
|
|
|
Phone #: ###-#### Inspection requested via web by Sam Reading
|
FIRE-Final Inspection | 3/11/2020 | 3/12/2020 | 3/12/2020 | A | PASS |
Jim Page
|
|
|
Previously noted item has been corrected, final life fire safety inspection is complete.
Phone #: ###-#### Inspection requested via web by Sam Reading
|
FIRE-Final Inspection | 3/10/2020 | 3/11/2020 | 3/11/2020 | A | FAIL |
Jim Page
|
|
|
Could not test release function on north stairwell door due to wiring issue, will need to retest release after repair is made.
Test remote unlock switch for L5 stairwell doors. Phone #: ###-#### Inspection requested via web by Sam Reading
|
FIRE-Final Inspection | 3/2/2020 | 3/3/2020 | 3/3/2020 | A | CANC |
Jim Page
|
|
|
Code exceptions done. Need final ok for c of o Phone #: ###-#### >> Inspection requested via web by Sam Reading Inspection cancelled from web by: Sam Reading
|
BLD-Final | 3/2/2020 | 3/3/2020 | 3/3/2020 | A | CANC |
Dave Hannah
|
|
|
Code exceptions done. Need final ok for c of o Phone #: ###-#### >> Inspection requested via web by Sam Reading Inspection cancelled from web by: Sam Reading
|
BLD-Final | 2/14/2020 | 2/18/2020 | 2/18/2020 | A | PART |
Dave Hannah
|
|
|
Phone #: ###-#### Inspection requested via web by Sam Reading ok for tco ok for co after fire gos perm
|
FIRE-Final Inspection | 2/14/2020 | 2/18/2020 | 2/18/2020 | A | PART |
Jim Page
|
|
|
Partial final inspection for life fire safety is complete for area of work. Fire sprinkler inspection is complete, fire alarm inspection is complete and NFPA72 compliant, waiting on as-builts to be submitted/approved for candella change in corner offices, fire alarm permit can be finaled after fire alarm permit is back in issued status. A formal letter of approveal to the building code official is required from the architect requesting the 2018 chapter 10 IFC exception for stairwell doors to be allowed locked and release on fire alarm activation as well as the combination tumbler look setup on the file room door and secure storage directly south of the file room. Combination looks do not meet IFC requirements for single action operation and will require approval from the building code official. 30 day TCO authorized by Joe Bruce, Fire Section Supervisor.
Phone #: ###-#### Inspection requested via web by Sam Reading
|
FIRE-Final Inspection | 2/13/2020 | 2/14/2020 | 2/14/2020 | P | FAIL |
Troy Cobbley
|
|
|
Provide all of the small documents, provide letter from the architect for compliance with the 2018 IFC 1010.1.9.11 exception #3, repair the exit sign in the 4th floor conference room.
Phone #: ###-#### Inspection requested via web by Sam Reading
|
BLD-Final | 2/13/2020 | 2/14/2020 | 2/14/2020 | P | CANC |
Brandon Shaw
|
|
|
Phone #: ###-#### >> Inspection requested via web by Sam Reading Inspection cancelled from web by: Sam Reading
|
FIRE-Conference | 2/7/2020 | 2/7/2020 | 2/7/2020 | A | DONE |
Jim Page
|
|
|
Fire conference complete, discussed items for life fire safety inspection. All door hardware to include delayed egress needs to in place and functional. Stairwell card readers needs to comply with 2015 IFC section 1010.1.9.11 per conversation with Joe Bruce, Fire Section Supervisor.
|
FIRE-Final Inspection | 2/4/2020 | 2/7/2020 | 2/7/2020 | A | CANC |
Jim Page
|
|
|
Was suppose to be scheduled as conference instead of final, this request is cancelled.
Phone #: ###-#### Inspection requested via web by Sam Reading
|
BLD-Final | 2/7/2020 | 2/7/2020 | 2/7/2020 | P | CANC |
Dave Hannah
|
|
|
Phone #: ###-#### >> Inspection requested via web by Sam Reading Inspection cancelled from web by: Sam Reading
|
BLD-Final | 2/4/2020 | 2/7/2020 | 2/7/2020 | A | CANC |
Dave Hannah
|
|
|
Phone #: ###-#### >> Inspection requested via web by Sam Reading Inspection cancelled from web by: Sam Reading
|
BLD-Ceiling Grid Inspection | 1/31/2020 | 1/31/2020 | 1/31/2020 | P | PASS |
Dave Hannah
|
|
|
Cover inspection for 4th floor Conference and break room. Phone #: ###-#### Inspection requested via web by Sam Reading
|
BLD-Ceiling Grid Inspection | 1/15/2020 | 1/16/2020 | 1/16/2020 | A | PASS |
Dave Hannah
|
|
|
Cover inspection for level 5, West and Northwest corridors and offices. Phone #: ###-#### Inspection requested via web by Sam Reading
|
BLD-Ceiling Grid Inspection | 1/13/2020 | 1/13/2020 | 1/13/2020 | P | PASS |
Dave Hannah
|
|
|
inspection for cover Level 5 from Gridline-C south Phone #: ###-#### Inspection requested via web by Sam Reading
|
BLD-Ceiling Grid Inspection | 1/7/2020 | 1/7/2020 | 1/8/2020 | P | PART |
Dave Hannah
|
|
|
Grid inspection east of elevators. excepting corridors, admin storage room, and mail room. Phone #: ###-#### Inspection requested via web by Sam Reading offices and hallway east side ok
|
FIRE-Conference | 12/24/2019 | 12/30/2019 | 12/30/2019 | A | DONE |
Jim Page
|
|
|
Fire conference complete.
Emergency light fixture layout, workstation furniture, additional signage requirements Phone #: ###-#### Inspection requested via web by Sam Reading
|
BLD-Wall cover | 12/5/2019 | 12/5/2019 | 12/11/2019 | P | PASS |
Dave Hannah
|
|
|
L4 shaft wall. Fire-rated enclosure under stairs Phone #: ###-#### Inspection requested via web by Sam Reading
|
BLD-Wall cover | 11/18/2019 | 11/18/2019 | 11/21/2019 | P | PASS |
Dave Hannah
|
|
|
Fire rating at 4th floor demising wall. Phone #: ###-#### Inspection requested via web by Sam Reading
|
BLD-Framing/Rough-in | 11/19/2019 | 11/20/2019 | 11/20/2019 | A | PART |
Dave Hannah
|
|
|
Ceiling cover for hardlids on level 5 Phone #: ###-#### Inspection requested via web by Sam Reading hard lids ok to cover
|
BLD-Wall cover | 10/30/2019 | 10/30/2019 | 10/30/2019 | P | PASS |
Dave Hannah
|
|
|
Fire Treated Plywood inspection for south stair interior wall and Secure store room West. Phone #: ###-#### Inspection requested via web by Sam Reading
|
BLD-Wall cover | 10/11/2019 | 10/14/2019 | 10/14/2019 | P | PASS |
Dave Hannah
|
|
|
Fire treated plywood walls L5 corridors and East Phone #: ###-#### Inspection requested via web by Sam Reading
|
BLD-Conference | 9/18/2019 | 9/19/2019 | 9/19/2019 | A | DONE |
Dave Hannah
|
|
|
Inspector requirements for Tenant build-out Phone #: ###-#### Inspection requested via web by Sam Reading
|