BLD-Final | 8/2/2019 | 8/2/2019 | 8/2/2019 | P | PASS |
Dave Hannah
|
|
|
Laren Phone #: ###-####
|
FIRE-Final Inspection | 8/2/2019 | 8/2/2019 | 8/2/2019 | P | PASS |
Jim Page
|
|
|
Fire sprinkler inspection is complete, fire alarm inspection is complete, outlets for VR units shunt during fire alarm activation, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete.
|
BLD-Final | 7/31/2019 | 8/1/2019 | 8/1/2019 | P | CANC |
Tell Riley
|
|
|
Leren Phone #: ###-####//cancel per Leren//need to pass fire final//
|
FIRE-Final Inspection | 7/31/2019 | 8/1/2019 | 8/1/2019 | A | FAIL |
Mark Scharfen
|
|
|
E-lights/extinguisher in place. Tested interface for shunt with Protex on site. Manually turning on relay did shunt the breaker but did not work in normal operation. Told Leren and Protex that a fire alarm permit would need to be pulled and proof of a propper pretest before building or fire alarm final is to be called in again.
Leren Phone #: ###-####
|
DOC - Permit Finaled | 7/31/2019 | 7/31/2019 | 7/31/2019 | P | PASS |
Dave Hannah
|
|
|
|