Information based on query as of Wednesday, May 8, 2024.
Permit Information
Permit NumberELE14-03229
StatusFinaled
Name STEPHENS ELECTRIC INC
Site Address 4405 W CATALPA DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - New: Wiring for a completely remodeled and new addition home
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/1/20154/1/20154/1/2015PPASS
DetailsDaryl DeGrange
The access code is 1130 Phone #: ###-#### Inspection requested via web by Stephen Kren correction done, final ok
Final3/30/20153/31/20153/31/2015AFAIL
DetailsDaryl DeGrange
Any questions please let me know, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren Hall Bathroom 210.52(D) More than one basin, a receptacle is reqired adjacent to each basin location or one receptacle between the two basins. Stairway luminaires not working.
Final3/27/20153/30/20153/30/2015ACANC
DetailsDaryl DeGrange
Any questions please call, thx. Phone #: ###-#### >> Inspection requested via web by Stephen Kren Inspection cancelled from web by: Stephen Kren
Final3/24/20153/25/20153/25/2015ANR
DetailsDaryl DeGrange
Phone #: ###-#### Inspection requested via web by Stephen Kren Job not ready for final at this time
Rough-In Permanent Service12/18/201412/19/201412/19/2014APASS
DetailsCevyn Recla
The corrections have been made, any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren
corrections made, RI OK, PS, UG, N, OK
Rough-In Permanent Service12/17/201412/17/201412/17/2014PFAIL
DetailsCevyn Recla
Any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren
310.15B 4/0 AL SER, 60*, max amp rating is 150
300.4 bored holes, nm shall be protected through bored holes with less than 1 1/4 inch to framing member edge
210.70.3 lighting outlets required, attic space with equipment requiring servicing
334.30 nm cable shall be supported at intervals not exceeding 4 1/2 foot
320.23 NM shall be protected withing 6 feet of attic access
spoke to Terry
Rough-In Permanent Service12/16/201412/17/201412/17/2014ACANC
DetailsCevyn Recla
Any questions please let me know, thx, TW. Phone #: ###-#### >> Inspection requested via web by Stephen Kren Inspection cancelled from web by: Stephen Kren