Information based on query as of Wednesday, May 15, 2024.
Permit Information
Permit NumberELE19-00596
StatusFinaled
Name TRI STATE ELECTRIC
Site Address 415 S 8TH ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration: demo and relocate Jewelry shop equipment
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/5/20196/6/20196/6/2019APASS
DetailsRock A. Hudson
Contact: Ryan Mrachek Phone #: ###-#### Inspection requested via web by Deb Gooden
No card posted. Final ok
Electrical Rough-In4/11/20194/12/20194/12/2019APASS
DetailsRock A. Hudson
Contact: Ryan Mrachek Phone #: ###-#### Inspection requested via web by Deb Gooden
As per notes on building permit a seperate building permit and electrical permit is required for finish out of dwelling unit.
Walls and hardlids of dwelling unit rough in ok cover
Electrical Rough-In4/4/20194/5/20194/5/2019APASS
DetailsRock A. Hudson
partial final on the office only
on site contact Ryan mrachek Phone #: ###-#### Inspection requested via web by Deb Gooden
TCO for 2 offices OK.
Electrical Rough-In4/1/20194/2/20194/2/2019APASS
DetailsTom Saunders
Contact: Ryan Mracheck Phone #: ###-#### Inspection requested via web by Deb Gooden...
ok to cover demising wall up to panel...top and bottom of panel will be fire caulked...wall behind will be furred out
Electrical Rough-In3/14/20193/15/20193/15/2019APART
DetailsRock A. Hudson
Contact: Mike Ennis - wall rough-in please Phone #: ###-#### Inspection requested via web by Deb Gooden
Issue with demizing wall fire rating with panel located recessed in it. Suggested surface mounting in end of hall way as possible solution. Rough in ok cover offices and 1 side of demizing wall up to end where panel located.
Final3/4/20193/5/20193/5/2019APART
DetailsRock A. Hudson
Contact: Rick Badley Phone #: ###-#### Inspection requested via web by Deb Gooden
Down storage/shop area. tco ok
Electrical Rough-In2/22/20192/25/20192/25/2019APASS
DetailsRock A. Hudson
Contact: Brian Gee. Partial rough-in ceiling inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden
Basement storage receptacles fished in ceiling will be curface mounted. Walls and ceiling rough in ok cover