Information based on query as of Friday, April 26, 2024.
Permit Information
Permit NumberFIR14-00372
StatusIssued
Name VANGUARD FIRE & SECURITY INC
Site Address 575 S 13TH ST
Project NameRiver Of Life Rescue Mission
Customer Number 
ePlanReviewYes
Description
This permit scope of work is to replace the existing fire alarm system. A MANUAL SYSTEM WITH AUTOMATIC DETECTION IN CORRIDORS SERVING SLEEPING AREAS, A PULL STATION, SMOKE DETECTION ABOVE THE FACP, SPRINKLER SYSTEM MONITORING, ELEVATOR RECALL AND SHUNT FUNCTIONS, F/S DAMPER AND HVAC SHUTDOWN/MONITORING SHALL BE PROVIDED AS PART OF THIS SCOPE OF WORK. IN ADDITION, SYSTEM SMOKE DETECTORS WITH SOUNDER BASES WILL BE INSTALLED TO TAKE THE PLACE OF SINGLE STATION/MULTI STATION 120V SMOKE ALARMS.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Alarm Testing8/31/20149/3/20149/3/2014ANR
DetailsForrest France
Completed initial project walkthrough. Items noted include; adjust notification at locations marked on plans at the 3rd, 2nd and 1st floors, (cd settings, spacing, height AFF), provide WP device at a 2nd floor bathroom, relocate a/v at the 2nd floor TV room, provide SD at the 2nd floor NAC, monitor sprinkler tamper at the 1st floor elevator control, relocate a/v at the kitchen exit access, post signage at the door to the FACP room, provide lock at circut breaker, post points map per review comments, provide documents cabinet. Provide plan modification for resubmittal to reflect field changes such as deleted ID's, door mag relays, elevator hat, changed room uses, added 1st floor vestibule, new ceiling mount devices in place of wall mount, - include IP DACT in place of phone lines. Remove all non-functional devices and system components from the previous panel including MP, SD, HD, power supplies, etc. prior to final.
INSP-Alarm Testing8/26/20148/26/20148/29/2014PDEFR
DetailsForrest France
Phone #: ###-#### Inspection requested via web by Keith Olstrom
INSP-Alarm Testing8/14/20148/20/20148/19/2014PDEFR
DetailsForrest France
Rescheduled for next week per conversation with contractor.
INSP-Conference8/19/20148/19/20148/19/2014PDONE
DetailsForrest France
Regarding project inspection and testing schedule.
FIR-Aging Inspection8/5/20208/5/2020   
DetailsJim Page