INSP-Final Inspection | 8/28/2019 | 8/29/2019 | 8/29/2019 | P | PASS |
Jim Page
|
|
|
Final fire sprinkler inspection complete.
Contact Ken Orahood ###-#### 30 min prior to Final Insp. start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Supply line flush | 7/30/2019 | 7/31/2019 | 7/31/2019 | A | DONE |
Jim Page
|
|
|
Undergorund main line flush completed after piping repair was made. Repair observed, undergournd approved for cover.
Contact Ken Orahood ###-####30 min prior to Flush Insp start please. Ken would like to do this at 9:30 AM if possible.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Supply line flush | 7/29/2019 | 7/30/2019 | 7/30/2019 | A | FAIL |
Jim Page
|
|
|
Main line flush was not cooridnated with SUEZ for valve operation, flush will need to be rescheduled and cooridnated with SUEZ.
Contact Aaron Trimble ###-#### 30 min prior to Flush Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Conference | 7/15/2019 | 7/15/2019 | 7/15/2019 | P | DONE |
Jim Page
|
|
|
Fire conference complete.
Contact Aaron Trimble ###-#### 30 min prior to Insp Consult start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Final Inspection | 6/24/2019 | 6/24/2019 | 6/24/2019 | P | FAIL |
Jim Page
|
|
|
Relocate head in master closet as discussed. Pressure relief hose kept coming loose during flow test, still need to accomplish flow test. Raise head in closet next to mech room as discussed.
Contact Ken Orahood ###-#### Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Supply line flush | 8/21/2018 | 8/22/2018 | 8/22/2018 | A | DONE |
Jim Page
|
|
|
Underground main line flush complete.
Contact Leroy Anderson ###-#### Flush has been scheduled with Stacy Stuart at SUEZ all have confirmed a 9 am Start.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Sprinkler Rough-in | 8/16/2018 | 8/17/2018 | 8/17/2018 | A | PASS |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping/tenting complete, approved for cover.
Contact Brad Westbrook ###-#### - 30 min prior to RTC Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Sprinkler Rough-in | 8/8/2018 | 8/9/2018 | 8/9/2018 | A | FAIL |
Jim Page
|
|
|
Drawings on site are not city approved drawings, could not find the city stap. Head in main entry is blocked, head needs relocated. Add head under mid level stairs. Numerous heads throughout are overspaced, as stated in permit description max spacing is 18ft by 18ft. Re-route piping that is bent around HVAC flex-duct located in basement level.
Contact Brad Westbrook ###-#### 30 min before RTC Start please, if voice mailbox is full please contact Leroy Anderson ###-#### please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Sprinkler Rough-in/Hydro | 7/31/2018 | 8/2/2018 | 8/2/2018 | P | CANC |
Jim Page
|
|
|
Attempted to call point of contact provided 2 times, could not leave a message because voicemail was full, this request is cancelled and a new inspection will need to be requested.
Contact Brad Westbrook - ###-#### 30 min prior to RTC insp Start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Sprinkler Rough-in | 7/12/2018 | 7/13/2018 | 7/13/2018 | A | PASS |
Jim Page
|
|
|
Undergorund piping has been changed to CPVC, undergorund supply approved for cover.
Contact Brad Westbrook ###-#### 30 min prior to UG RTC Insp Start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Sprinkler Rough-in | 7/6/2018 | 7/6/2018 | 7/6/2018 | P | FAIL |
Troy Cobbley
|
|
|
Per the plumbing inspector the underground piping being used is not listed. LIsted piping needs to be installed and re-inspected.
Contact Brad Westbrook - ###-#### 30 min prior to UG RTC Start please, hew would prefer to schedule this inspection for 2pm today.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Conference | 7/3/2018 | 7/3/2018 | 7/3/2018 | P | DONE |
Jim Page
|
|
|
Fire conference complete for undeground supply.
|
INSP-Sprinkler Rough-in | 7/2/2018 | 7/3/2018 | 7/3/2018 | P | CANC |
Jim Page
|
|
|
Request was for a conference on the underground, this request is cancelled.
Contact Brad Westbrook - ###-#### 30 Min prior to Insp. start, Brad needs this to be after 1PM if at all possible please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|