Permit Information
Permit NumberFIR18-00139
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1410 N ETHRIDGE LN
Project NameBOISE DAY CARE
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of protecting an existing structure with a new wet pipe system. The system will be supplied by new 4”x100’± C900 underground piping.
[BLD16-NA]
Alternative Materials and Methods:
This project includes approved code alternates to the following fire protection systems and/or building life safety systems. Please review the supplemental documents attached to this building permit case for details. Fire protection “shop drawings” shall include approved code alternate design.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/26/20197/29/20197/29/2019APASS
DetailsTroy Cobbley
permit finaled

Nate Phone #: ###-#### Inspection requested via web by Nathan Stenquist
INSP-Final Inspection7/26/20197/26/20197/26/2019PCANC
DetailsTroy Cobbley
Nate Phone #: ###-#### >> Inspection requested via web by Nathan Stenquist Inspection cancelled from web by: Nathan Stenquist
INSP-Final Inspection7/22/20197/26/20197/26/2019AFAIL
DetailsTroy Cobbley
Building is locked. No inspection performed


Phone #: ###-#### Inspection requested via web by Nathan Stenquist
INSP-Sprinkler Rough-in3/5/20193/6/20193/6/2019APASS
DetailsTroy Cobbley
Rough in passed. Fire alarm tie in passed. Apoproved for cover. Final can be signed off after ceiling tile is installed.

mike Phone #: ###-####
INSP-Sprinkler Rough-in3/4/20193/5/20193/5/2019PCANC
DetailsTroy Cobbley
Mike Phone #: ###-####
INSP-Final Inspection2/19/20192/20/20192/20/2019PCANC
DetailsTroy Cobbley
Not ready for a final yet. Missing ceiling tile and the project related fire alarm was not ready. Mike Phone #: ###-####
INSP-Sprinkler Rough-in8/27/20188/27/20188/27/2018APASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping complete, approved for cover.
INSP-Sprinkler Rough-in/Hydro8/27/20188/27/20188/27/2018PDONE
DetailsJim Page
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss at riser provided gauge.

Mike Phone #: ###-####
INSP-Supply line flush7/16/20187/17/20187/17/2018APASS
DetailsTroy Cobbley
Underground supply line flush passed


Troy Phone #: ###-####
INSP-Sprinkler Rough-in/Hydro7/13/20187/13/20187/13/2018PPASS
DetailsTroy Cobbley
underground hydro test passed

- Troy Phone #: ###-####
INSP-Sprinkler Rough-in/Hydro7/12/20187/12/20187/12/2018PFAIL
DetailsTroy Cobbley
Underground hydro test failed due to visible loss on the guage.

Troy Phone #: ###-####
INSP-Sprinkler Rough-in5/3/20185/4/20185/4/2018APASS
DetailsTroy Cobbley
The remaining underground piping is ok for cover.
INSP-Sprinkler Rough-in4/20/20184/20/20184/20/2018PPART
DetailsJim Page
Rough to cover inspection for change of direction, PIV and piping between change of direction and PIV complete, approved for cover. Piping after PIV to be installed at a later date.
INSP-Sprinkler Rough-in4/19/20184/19/20184/19/2018PPART
DetailsJim Page
Partial rough to cover inspection complete for underground supply, approximately 100 feet of west to east section approved for cover. Change of direction to the north, the PIV and stub in to be scheduled for a later date.