Permit Information
Permit NumberFIR18-00235
StatusFinaled
Name BOISE SCHOOL DIST
Site Address 3536 W HILL RD
Project NameHillside Jr High AES
Customer Number 
ePlanReviewYes
Description
THIS PROJECT SCOPE IS TO TIE A NEW AES INTELLINET RF COMMUNICATOR TO THE EXISTING MAXSYS FIRE ALARM COMMUNICATOR IN ORDER TO ELIMINATE TELEPHONE LINES AT THE SITE.
This work is not associated with a building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/2/20194/3/20194/3/2019PPASS
DetailsJim Page
Final AES inspection complete.

as late in pm as possible - can't have alarms go off during school // Will Phone #: ###-####
INSP-Final Inspection3/22/20193/22/20193/22/2019PFAIL
DetailsJim Page
Trouble restores with monitoring when a general fire alarm is sent even though fire panel is still in trouble.

Bill Phone #: ###-####
INSP-Final Inspection3/20/20193/21/20193/21/2019AFAIL
DetailsJim Page
Valve on fire sprinkler system reports out as a trouible, when fire alarm panel is in trouble, each subsequent trouble does not report out until panel is reset.

Bill Phone #: ###-####
INSP-Final Inspection3/14/20193/15/20193/15/2019AFAIL
DetailsJim Page
AES did not show NETCON 5.

Jacob Phone #: ###-####
INSP-Final Inspection3/14/20193/14/20193/14/2019PFAIL
DetailsJim Page
Put panel into trouble, trouble signal was recieved at central station, sent a general alarm and trouble restored at central station. Issue needs to be resloved and panel needs to be tested with real events and not shorting contacts.

Jacob Phone #: ###-####