Information based on query as of Saturday, May 11, 2024.
Permit Information
Permit NumberFIR18-00319
StatusFinaled
Name THORPE FIRE SPRINKLER SYSTEMS
Site Address 1779 N MOCKBEE PL
Project Name1779 MOCKBEE RESIDENCE
Customer Number 
ePlanReviewYes
Description
[10-1 Sherman]
The fire sprinkler scope of work consists of protecting a single family dwelling with a passive purge system.
[BLD18-00667]
Permit for the construction of a new 2871 sq. ft., two story (first story 1647 sq. ft., second story 1224 sq. ft.) single family dwelling with 4 bedrooms, 3.5 bathrooms, approximately 372 sq. ft. of covered patio/porch and a 766 sq. ft. attached garage per the approved plans, plan review report and any notations. R-1B zoning and setbacks per planning. MDH

Alternative Materials and Methods:

• There are no AMM at this time.
Plan Mod 2/5/2019 Approved **MAS**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/2/20194/3/20194/3/2019PPASS
DetailsJim Page
Previously noted items have been corrected, final fire sprinkler inspection complete.

Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Final Inspection3/28/20193/29/20193/29/2019AFAIL
DetailsJim Page
4 heads to close to heat registers, a minimum of 24 inches is allowed per NFPA 13D. Head in master bathroom needs to be relocated to spray in shower area, walls of shower do not go all the way to the ceiling so shower is not a seperate compartment. Garage needs to be a conditioned spaces due to fire sprinkler install.

Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in10/12/201810/12/201810/12/2018PPASS
DetailsJim Page
All tenting in place at time of inspection, overhead fire sprinkler piping approved for cover.

Tenting inspection, call Anthony before heading out. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in/Hydro10/11/201810/11/201810/11/2018APART
DetailsJim Page
Rough in inspection for overhead fire sprinkler piping complete, sprinkler piping requiring tenting not approved for cover, all other fire sprinkler piping approved for cover.

Please call Anthony before heading out, thank you. Phone #: ###-#### Inspection requested via web by Anthony Minichiello