Permit Information
Permit NumberFIR18-00717
StatusFinaled
Name WEBSTER FIRE PROTECTION
Site Address 707 W FORT ST
Project NameIMMANUEL LUTHERAN CHURCH
Customer Number 
ePlanReviewYes
Description
THIS IS AN ADDITION TO A EXISTING FIRE ALARM IN A EXISTING BUILDING. Providing sprinkler monitoring to a new sprinkler zone. This work is associated with building permit BLD18-00887.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/28/20193/1/20193/1/2019APASS
DetailsJim Page
Final fire alarm inspection to include as-builts complete.

Buck Phone #: ###-####
INSP-Final Inspection1/31/20192/1/20192/1/2019APASS
DetailsJim Page
Previously noted items have been corrected, final fire alarm inspection complete.


Phone #: ###-#### Inspection requested via web by Ken Webster
INSP-Final Inspection1/21/20191/22/20191/22/2019AFAIL
DetailsJim Page
Provide notification in areas as discussed. Pressure switch on dry system needs to be connected to FDC bell. Lower device in chapel area that is too high.

Plans will need to be resubmitted for areas that needs devices added and for areas where work was completed.

###-#### Ken Webster Phone #: ###-#### Inspection requested via web by Ken Webster