INSP-Final Inspection | 7/16/2019 | 7/17/2019 | 7/17/2019 | P | PASS |
Jim Page
|
|
|
Final fire sprinkler inspection for scope of work complete.
Please call Clarence Phone #: ###-#### Inspection requested via web by Jessia Maxwell
|
INSP-Sprinkler Rough-in | 6/18/2019 | 6/18/2019 | 6/18/2019 | P | PASS |
Jim Page
|
|
|
Rough in inspection for new overhead fire sprinkler piping below new hardlid in area of work complete. Insulation has been moved to above sprinkler piping in attic space.
chris Phone #: ###-####
|
INSP-Sprinkler Rough-in | 5/22/2019 | 5/22/2019 | 5/22/2019 | P | FAIL |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping in attic space where piping was removed and installed due to roof collapse complete. Insulation is shown to be installed on the bottom cords of the trusses, piping will not be protected from freezing with this application. Freeze protection will need to be provided for fire sprinkler piping in attic space or submit heat calculations from a professional engineer showing that the attic space will be maintained at a minimum of 40 degrees fahrenheit to be compliant with 2016 NFPA 13, section 8.16.4.
###-#### clarence
|