Permit Information
Permit NumberFIR19-00359
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 1075 N CURTIS RD
Project NameSARMC Vascular Clinic Remodel
Customer Number 
ePlanReviewYes
Description
4,945 sq ft single level bldg remodel Per NFPA13, 2016 Code Occupancy Class B, Construction Type II B
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/21/201910/22/201910/22/2019APASS
DetailsTroy Cobbley
Permit finaled

Contact Ken Orahood ###-#### 30 Min prior to Final Insp start please

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in9/13/20199/13/20199/13/2019PPASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.

Contact Noemi Carrero - ###-#### 30min prior to RTC Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in8/1/20198/2/20198/2/2019PPASS
DetailsTroy Cobbley
Rough-in passed. Will need another rough to cover inspection once the flex heads have been placed.

Contact Tanner Loomis ###-#### 30 Min prior to RTC Insp strart please

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in8/1/20198/1/20198/1/2019PNR
DetailsTroy Cobbley
The contractor scheduled the wrong permit/job. I still spoke to the fitter and general contractor about the sprinkler modifications. An inspection for this project will be scheduled for tomorrow.

Contact Tyler Loomis ###-#### 30 min prior to RTC insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in7/29/20197/30/20197/30/2019PFAIL
DetailsTroy Cobbley
Provide plan modifications/hydraulic calculations showing the actual piping layout now that two pendant heads are being piped from a single 1" outlet. Contact Tanner Loomis ###-#### 30 min prior to RTC Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in7/25/20197/26/20197/26/2019APASS
DetailsTroy Cobbley
See the city approved plans for the four locations where piping can be covered above the hard lids.

Contact Tanner Loomis - ###-#### 30 min prior to RTC Insp Start please, RTC is for Hard Lid heads only.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank