Permit Information
Permit NumberFIR19-00404
StatusIssued
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 2470 N ASHGROVE LN
Project NameASHGROVE RESIDENCE
Customer Number 
ePlanReviewYes
Description
SHILO WILL START AFTER A BACKFLOW INSTALLED BY A PLUMBER AND INSTALL CPVC PIPE AND 4.9K CONCEALED HEADS TO PROTECT THE ASHGROVE RESIDENCE. TENTING SHALL BE BY OTHERS. THIS IS A SHARED WATER LINE. THE LAWN SPRINKLERS SHALL BE PROGRAMMED TO SHUT OFF WHEN FIRE SPRINKLERS ACTIVATE - DONE BY THE ELECTRICIAN.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/29/201910/30/201910/30/2019AFAIL
DetailsJim Page
Provide annual inspection for backflow assembly. Repair visible leak at bottom of backflow.

Bobbie Silva is the contact. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Final Inspection10/18/201910/21/201910/21/2019PFAIL
DetailsTroy Cobbley
Water has not been piped to the riser.

Jon Beazer is the contact. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Final Inspection10/17/201910/18/201910/18/2019ACANC
DetailsTroy Cobbley
Cancel per Jon Beazer since he can not be there when I can be there. . We appreciate your help. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in7/3/20197/3/20197/3/2019APASS
DetailsJim Page
Rough to cover ispection for overhead fire sprinkler piping complete, all tenting in place at time of insulation, approved for cover.
INSP-Sprinkler Rough-in/Hydro7/2/20197/3/20197/3/2019ADONE
DetailsJim Page
Hydrostatic test for overhead fire sprinkler piping witnessed at 150PSI, above what is required by 13D, no pressure loss observed.

Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus