Permit Information
Permit NumberFIR19-00445
StatusFinaled
Name PROTEX
Site Address 2015 N CURTIS RD
Project NameKoelsch Cafeteria Bldg.
Customer Number 
ePlanReviewYes
Description
Add Voice Fire Alarm Panel panel to new cafeteria building. This work is associated with BLD18-04112.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/16/201910/17/201910/17/2019APASS
DetailsTroy Cobbley
Permit finaled.

Contact is Morgan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection10/14/201910/14/201910/14/2019PFAIL
DetailsTroy Cobbley
Need as-builts showing the candella change and the added duct smoke detector. Contact is Dirk. Client requests final for after school hours. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection10/2/201910/3/201910/3/2019PFAIL
DetailsTroy Cobbley
Ceiling mounted strobes are overspaced in the Kitchen. Inspection stopped. Devices need to be relocated or candellas adjusted. The fire alam plans need to be reviewed by the engineer of record prior to plan review approval. Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten