INSP-Final Inspection | 10/16/2019 | 10/17/2019 | 10/17/2019 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled.
Contact is Morgan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Final Inspection | 10/14/2019 | 10/14/2019 | 10/14/2019 | P | FAIL |
Troy Cobbley
|
|
|
Need as-builts showing the candella change and the added duct smoke detector. Contact is Dirk. Client requests final for after school hours. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Final Inspection | 10/2/2019 | 10/3/2019 | 10/3/2019 | P | FAIL |
Troy Cobbley
|
|
|
Ceiling mounted strobes are overspaced in the Kitchen. Inspection stopped. Devices need to be relocated or candellas adjusted. The fire alam plans need to be reviewed by the engineer of record prior to plan review approval. Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|