INSP-Final Inspection | 10/24/2019 | 10/25/2019 | 10/25/2019 | A | PASS |
Jim Page
|
|
|
Previously noted items have been corrected, final fire alarm inspection is complete.
Phone #: 208831311 >> Inspection requested via mobile web by Nathan Price
|
INSP-Final Inspection | 10/21/2019 | 10/22/2019 | 10/22/2019 | A | FAIL |
Jim Page
|
|
|
Reloacte audio visual device tghat is blocked by ductwork. Mag locks on access control are not interfaced with fire alarm system, per IFC access controled mag lock doors must release on general fire alarm. Provide weather proof audio visual devices in restrooms, no header/lintel provided in shower area making it a seperate compartment. Provide A/V device in staff locker room as discussed.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
INSP-Final Inspection | 10/18/2019 | 10/21/2019 | 10/21/2019 | P | CANC |
Troy Cobbley
|
|
|
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price Inspection cancelled via mobile web on Monday, October 21, 2019.
|
INSP-Alarm Testing | 10/18/2019 | 10/18/2019 | 10/18/2019 | P | CANC |
Jim Page
|
|
|
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price Inspection cancelled via mobile web on Friday, October 18, 2019.
|