Final | 2/22/2019 | 2/25/2019 | 2/25/2019 | A | PASS |
Brian Scoles
|
|
|
final Phone #: ###-#### Inspection requested via web by Brandon Sorensen- HVAC and fireplace final ok
|
Final | 2/18/2019 | 2/19/2019 | 2/19/2019 | P | FAIL |
Brian Scoles
|
|
|
final re-insection Phone #: ###-#### Inspection requested via web by Brandon Sorensen- need sediment trap on unit heater gas piping between shutoff valve and appliance- mantel height needs to be addressed Dave looking into this
|
Final | 2/12/2019 | 2/13/2019 | 2/13/2019 | A | FAIL |
Brian Scoles
|
|
|
final - garage code #9604 Phone #: ###-#### Inspection requested via web by Brandon Sorensen- mantel height to low per manufactures installation instructions need to move up- 2nd drain needs ran or wet switch instlled- pvc furnace flue needs clearance to combustibles unit heat fluing- R/A needs insulated- need balance report onsite- drip leg on furnace and unit heater- seal gas line and lineset penterations weather tight outside
|
Final | 2/6/2019 | 2/6/2019 | 2/6/2019 | P | NH |
Brian Scoles
|
|
|
final Phone #: ###-#### Inspection requested via web by Brandon Sorensen- no access
|
Rough-in | 10/9/2018 | 10/10/2018 | 10/10/2018 | P | PASS |
Brian Scoles
|
|
|
Reinspect Inspection requested via web by Brandon Sorensen- fireplace and hvac R/I ok
|
Pressure Test | 10/9/2018 | 10/10/2018 | 10/10/2018 | P | PASS |
Brian Scoles
|
|
|
Reinspect Phone #: ###-#### Inspection requested via web by Brandon Sorensen- 60lb gas pass- tagged pipe by meter
|
Rough-in | 10/8/2018 | 10/9/2018 | 10/9/2018 | A | FAIL |
Brian Scoles
|
|
|
rough Phone #: ###-#### Inspection requested via web by Brandon Sorensen- ducting in crawl and ceiling needs insulated to pass R/I- need to install 2x4 in wall 2nd floor below wall exhaust fan- rest is good
|
Pressure Test | 10/8/2018 | 10/9/2018 | 10/9/2018 | A | FAIL |
Brian Scoles
|
|
|
pressure test Phone #: ###-#### Inspection requested via web by Brandon Sorensen- gauge at zero psi-
|
Rough-in | 10/3/2018 | 10/4/2018 | 10/4/2018 | A | NR |
Brian Scoles
|
|
|
rough in Phone #: ###-#### Inspection requested via web by Brandon Sorensen- need to resubmit manual j showing system thats installed- doesnt match approved man j
|
Pressure Test | 10/3/2018 | 10/4/2018 | 10/4/2018 | A | FAIL |
Brian Scoles
|
|
|
pressure test Phone #: ###-#### Inspection requested via web by Brandon Sorensen- hard pipe needs to extend into fireplace- retest when complete
|