Final | 5/31/2019 | 6/3/2019 | 6/3/2019 | A | PASS |
Brian Scoles
|
|
|
Garage code: 2102 Replaced kitchen hood vent with rigid duct Replaced water heater vent with B vent Phone #: ###-#### Inspection requested via web by Michael Stimpson
|
Final | 5/30/2019 | 5/31/2019 | 5/31/2019 | A | FAIL |
Brian Scoles
|
|
|
garage code 2102 Phone #: ###-#### Inspection requested via web by Michael Stimpson- range duct needs ran insmooth interior metal no flex duct- water heater flue needs 6" clearance to conbustibles for single wall pipe
|
Rough-in | 12/31/2018 | 12/31/2018 | 12/31/2018 | P | PASS |
Jack Reynolds
|
|
|
Inspection requested via web by Michael Stimpson - 5lb flue pressure test ok - R/I ok
|
Rough-in | 12/28/2018 | 12/31/2018 | 12/31/2018 | A | FAIL |
Jack Reynolds
|
|
|
Ready for pressure test inspection Inspection requested via web by Michael Stimpson - gauge was under 5lb
|
Rough-in | 12/27/2018 | 12/28/2018 | 12/28/2018 | A | FAIL |
Jack Reynolds
|
|
|
B-vent has been covered in attic. Pressure test ready for inspection Inspection requested via web by Michael Stimpson - 5lb flue pressure test fail gauge was under 5lb - water heater insulation sheild ok
|
Rough-in | 12/22/2018 | 12/24/2018 | 12/24/2018 | A | FAIL |
Jack Reynolds
|
|
|
garage code 2102 Phone #: ###-#### Inspection requested via web by Michael Stimpson - dryer exhaust ok - exhaust fan ok - clearances for water heater b vent look ok in the wall but b vent still needs an insulation sheild in the attic. some old insulation in the attic is touching vent - need to see 5lb flue test before R/I gets passed
|
Rough-in | 12/11/2018 | 12/12/2018 | 12/12/2018 | P | FAIL |
Jack Reynolds
|
|
|
garage code in case no one is there: 2102 Phone #: ###-#### Inspection requested via web by Michael Stimpson - 1" clearances on water heater b vent in several locations. Also 1" clearances once sheet rock is installed - 1 exhaust fan upstairs is not finished and connection needs sealed - need to see a 5lb flue pressure test before ceiling cover - dryer vent needs to be independent. can't common vent bathroom exhaust and dryer together
|