Information based on query as of Tuesday, May 14, 2024.
Permit Information
Permit NumberMEC18-05852
StatusFinaled
Name SNOWFLAKE AIR LLC
Site Address 5928 W ELKHORN AVE
Project Name 
Customer Number2717
ePlanReviewNo
Description
Alteration or Repair: Complete furnace installation. Reinstall AC. Install new bathroom/laundry vents. Install supplies to basement bedrooms.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/31/20196/3/20196/3/2019APASS
DetailsBrian Scoles
Garage code: 2102
Replaced kitchen hood vent with rigid duct
Replaced water heater vent with B vent Phone #: ###-#### Inspection requested via web by Michael Stimpson
Final5/30/20195/31/20195/31/2019AFAIL
DetailsBrian Scoles
garage code 2102 Phone #: ###-#### Inspection requested via web by Michael Stimpson- range duct needs ran insmooth interior metal no flex duct- water heater flue needs 6" clearance to conbustibles for single wall pipe
Rough-in12/31/201812/31/201812/31/2018PPASS
DetailsJack Reynolds
Inspection requested via web by Michael Stimpson
- 5lb flue pressure test ok
- R/I ok
Rough-in12/28/201812/31/201812/31/2018AFAIL
DetailsJack Reynolds
Ready for pressure test inspection Inspection requested via web by Michael Stimpson
- gauge was under 5lb
Rough-in12/27/201812/28/201812/28/2018AFAIL
DetailsJack Reynolds
B-vent has been covered in attic. Pressure test ready for inspection Inspection requested via web by Michael Stimpson
- 5lb flue pressure test fail gauge was under 5lb
- water heater insulation sheild ok
Rough-in12/22/201812/24/201812/24/2018AFAIL
DetailsJack Reynolds
garage code 2102 Phone #: ###-#### Inspection requested via web by Michael Stimpson
- dryer exhaust ok
- exhaust fan ok
- clearances for water heater b vent look ok in the wall but b vent still needs an insulation sheild in the attic. some old insulation in the attic is touching vent
- need to see 5lb flue test before R/I gets passed
Rough-in12/11/201812/12/201812/12/2018PFAIL
DetailsJack Reynolds
garage code in case no one is there: 2102 Phone #: ###-#### Inspection requested via web by Michael Stimpson
- 1" clearances on water heater b vent in several locations. Also 1" clearances once sheet rock is installed
- 1 exhaust fan upstairs is not finished and connection needs sealed
- need to see a 5lb flue pressure test before ceiling cover
- dryer vent needs to be independent. can't common vent bathroom exhaust and dryer together