Permit Information
Permit NumberMEC19-00733
StatusFinaled
Name ICON AIR
Site Address 9647 W BURNETT DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete HVAC Installation: Installing HVAC and fireplace
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/12/20194/12/20194/12/2019PPASS
DetailsBrian Scoles
approved man J now on site and balance report was in lit rack in furnace closet.
Re inspection
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- HVAC and fireplace final ok
Final4/8/20194/11/20194/11/2019AFAIL
DetailsBrian Scoles
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- need approved man j and air balance report onsite none could be found
Rough-in2/26/20192/27/20192/27/2019PPASS
DetailsBrian Scoles
re inspection 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- R/

I ok
Rough-in2/25/20192/26/20192/26/2019PFAIL
DetailsBrian Scoles
re inspection code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- all corrections not made- need to insulate wye branch front entry door bare metal showing- water heater b vent needs 1" clearance to plywood where b vent goes thru 1st floor ceiling in chase from garage- correction notice still posted front entry window
Pressure Test2/25/20192/26/20192/26/2019PPASS
DetailsBrian Scoles
re inspection code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- 20lb gas pass- tagged meter location-
Rough-in2/19/20192/25/20192/25/2019AFAIL
DetailsBrian Scoles
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart-
1) need approved manual j onsite no prints could be found
2) water heater flue needs 1" clearance to combustibles in garage at ceiling
3) all R/A and supply boots need sealed
4) fireplace thimble inside exterior wall upside down doesnt meet clearance per installation instructions
5) outside air can needs insulated and sealed in attic where ties onto R/A plenum
6)R/A ducting off top of plenum needs to be secured father away from b vent in attic
7)supply wye branches need insulated in a couple places in attic bare metal showing
8) gas test failed gauge wont zero out-

left correction notice front entry window
Pressure Test2/19/20192/25/20192/25/2019AFAIL
DetailsBrian Scoles
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- gauge wont zero out