Final | 1/7/2020 | 1/8/2020 | 1/8/2020 | A | PASS |
Brian Scoles
|
|
|
Garage Code: 1234 If this does not work please contact Sam with Simplicity Homes ###-#### Phone #: ###-#### Inspection requested via web by Terek Worley
|
Final | 1/6/2020 | 1/6/2020 | 1/6/2020 | P | FAIL |
Jack Reynolds
|
|
|
garage code 1234 Phone #: ###-#### Inspection requested via web by Terek Worley - need locking caps installed on A/C
|
Rough-in | 10/17/2019 | 10/18/2019 | 10/18/2019 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Terek Worley- R/I ok
|
Rough-in | 10/15/2019 | 10/15/2019 | 10/15/2019 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Terek Worley 1- need to insulate outside air filter box to r-6 not r-4.2 2- need to remove 6" tap on R/A can and patch/seal and insulate to r-6
reinspection fee issued
|
Rough-in | 9/27/2019 | 9/27/2019 | 9/27/2019 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Terek Worley- corrections not all done- see correction notice front entry window
|
Rough-in | 9/26/2019 | 9/26/2019 | 9/26/2019 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Terek Worley- 1- need to insulate outside air filter box in attic 2- supply register in master bedroom just hanging in ceiling 3- 6" fresh/outside air can not come from register can needs tied into R/A plenum at furnace 4- need 4" b vent 90 at furnace location in attic
left notice front entry window
|
Pressure Test | 9/26/2019 | 9/26/2019 | 9/26/2019 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Terek Worley- 20lb gas pass
|
Pressure Test | 9/24/2019 | 9/25/2019 | 9/24/2019 | A | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### >> Inspection requested via web by Terek Worley Inspection cancelled from web by: Terek Worley
|
Rough-in | 9/24/2019 | 9/25/2019 | 9/24/2019 | A | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### >> Inspection requested via web by Terek Worley Inspection cancelled from web by: Terek Worley
|