Permit Information
Permit NumberMEC19-04289
StatusFinaled
Name AMERICAN MECHANICAL
Site Address 2855 W LOCKHEED LN
Project Name 
Customer Number 
ePlanReviewNo
Description
Addition: 1. M21 changes as follows:
Demo
G,D,R''s
Relocating WC6
2. (2) Volume dampers for existing louvers per note 36 and 37 with accessories listed on M70
3. Fire Dampers as shown on print
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/2/20201/3/20201/3/2020APASS
DetailsJack Reynolds
Final Inspection - T ; B provided Phone #: ###-#### Inspection requested via web by Beka Hereau
- final ok
- occ card signed
Final11/7/201911/8/201911/8/2019APART
DetailsJack Reynolds
Temp Final for temp c of o Phone #: ###-#### Inspection requested via web by Beka Hereau
- partial final ok
- need to see balance report for final
- signed temp occ card
Rough-in11/5/201911/5/201911/5/2019PPASS
DetailsJack Reynolds
Rough In for cover Phone #: ###-#### Inspection requested via web by Beka Hereau
- R/I ceiling cover ok
Rough-in10/25/201910/28/201910/28/2019PPART
DetailsJack Reynolds
FIRE Damper Rough In - Inspection Phone #: ###-#### Inspection requested via web by Beka Hereau
- fire damper clearances ok
-all fire caulk needs to be removed and fire damper access doors installed by ceiling R/I
cover
- radiant heater flue clearnaces ok need to caulk all exhaust venting seams
Rough-in10/23/201910/24/201910/24/2019AFAIL
DetailsJack Reynolds
Rough In Inspection of Dampers - someone will be on site Phone #: ###-#### Inspection requested via web by Beka Hereau
- duct work ok
- still need proper installation instructions for round fire dampers. All angles need removed to check clearances. remove fire caulk on dampers unless instructions say to do so. Each fire damper will also need an access door installed.
- condensates for units ok
- exhaust side of radiant heaters needs sealed with high temp sealer and need to check clearances on vent throughn roof
Rough-in10/17/201910/18/201910/18/2019AFAIL
DetailsJack Reynolds
Rough In Inspection Phone #: ###-#### Inspection requested via web by Beka Hereau
- no access to location
- talking with Rich retaining angles on fire dampers will need to be removed and installation instructions be onsite for next inspection.
- Re schedule R/I inspection and fire damper inspection