Final | 12/13/2019 | 12/16/2019 | 12/16/2019 | A | PASS |
Brian Scoles
|
|
|
Inspection requested via web by jeff jedlick- final ok - card signed
|
Rough-in | 12/6/2019 | 12/6/2019 | 12/6/2019 | P | PASS |
Brian Scoles
|
|
|
Inspection requested via web by jeff jedlick- R/I ok- registers flex and insulation ok- ok for ceiling tiles- need air balance report onsite for hoo and MAU- need condensate drains on RTUs- need to label f/s damper access doors by final
|
Conference | 12/5/2019 | 12/5/2019 | 12/5/2019 | P | DONE |
Brian Scoles
|
|
|
Call when you have a minute Inspection requested via web by jeff jedlick-
|
Rough-in | 12/4/2019 | 12/4/2019 | 12/4/2019 | A | PART |
Brian Scoles
|
|
|
will need engineer approval on mau ducting that has changed sizing and routing
|
Rough-in | 11/25/2019 | 11/25/2019 | 11/25/2019 | A | PASS |
Brian Scoles
|
|
|
2 fire smoke damper clearances ok-
|
Rough-in | 11/20/2019 | 11/20/2019 | 11/20/2019 | P | PART |
Brian Scoles
|
|
|
I’m here all day, like to meet late as possible... Phone #: ###-#### Inspection requested via web by jeff jedlick- seal on remaining duct ok- ok to insulate- need to look at f/s damper clearances next inspection
|
Conference | 10/28/2019 | 10/28/2019 | 10/28/2019 | A | DONE |
Brian Scoles
|
|
|
Want to go over installation instructions on smoke/fire damper Inspection requested via web by jeff jedlick- went over fire/smoke damper installation
|
Rough-in | 10/25/2019 | 10/25/2019 | 10/25/2019 | P | PASS |
Brian Scoles
|
|
|
Inspection requested via web by jeff jedlick- bath room hardlids ok to cover- seal and insulation ok in bath room
|
Rough-in | 10/24/2019 | 10/24/2019 | 10/24/2019 | P | CANC |
Brian Scoles
|
|
|
Inspection requested via web by jeff jedlick- will reschedule per phone call
|
Conference | 10/23/2019 | 10/23/2019 | 10/23/2019 | P | DONE |
Brian Scoles
|
|
|
Inspect the bathroom ducting and fire wall penetration. 208 801 3772 Shawn general on the job Phone #: ###-#### Inspection requested via web by jeff jedlick- went over fire damper installation instructions- needs sleeve extending out on each side of wall- call in R/I when ready
|