Second Notice | | 7/19/2020 | 7/28/2020 | | DONE |
|
|
|
This permit finaled on the web by Caloub Huttash
|
First Notice | | 5/22/2020 | 7/9/2020 | | DONE |
|
|
|
mailed 7-9-2020
|
Telephone call | | | 5/12/2020 | | DONE |
|
|
|
Confirmed with Jared from the Russel Corporation that ELE19-03525 was for both the TI and the Shell/Core.
|
Permanent Occupancy | | | 5/12/2020 | | DONE |
|
|
|
|
BLD-Final | 5/11/2020 | 5/11/2020 | 5/11/2020 | P | PASS |
Mike Jordan
|
|
|
Phone #: ###-#### Inspection requested via web by Jared Waggoner. Ok for perm occ.
|
Zoning Approval | 5/11/2020 | 5/11/2020 | 5/11/2020 | | PASS |
Katelyn Menuge
|
|
|
|
BLD-Conference | 5/6/2020 | 5/6/2020 | 5/6/2020 | P | DONE |
Mike Jordan
|
|
|
Phone #: ###-#### Inspection requested via web by Jared Waggoner
|
BLD-Final | 5/4/2020 | 5/4/2020 | 5/4/2020 | P | NR |
Mike Jordan
|
|
|
Phone #: ###-#### Inspection requested via web by Jared Waggoner
|
FIRE-Final Inspection | 5/4/2020 | 5/4/2020 | 5/4/2020 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed.
Phone #: ###-#### Inspection requested via web by Jared Waggoner
|
FIRE-Final Inspection | 4/29/2020 | 4/30/2020 | 4/30/2020 | P | FAIL |
Troy Cobbley
|
|
|
Permit can be finaled when the project related fire alarm permit and the Grading permit have been finaled. Jared Phone #: ###-####
|
BLD-Ceiling Grid Inspection | 3/25/2020 | 3/26/2020 | 3/26/2020 | P | PASS |
Mike Jordan
|
|
|
2nd floor 3 west offices for ceiling cover Phone #: ###-#### Inspection requested via web by Jared Waggoner
|
BLD-Ceiling Grid Inspection | 3/20/2020 | 3/20/2020 | 3/20/2020 | P | PART |
Mike Jordan
|
|
|
2nd floor ceiling grid for cover Phone #: ###-#### Inspection requested via web by Jared Waggoner. Grid ok pending electrical and mech. rough in inspection.
|
BLD-Ceiling Grid Inspection | 3/16/2020 | 3/17/2020 | 3/17/2020 | P | PASS |
Mike Jordan
|
|
|
First floor ceiling grid Phone #: ###-#### Inspection requested via web by Jared Waggoner
|
BLD-Framing/Rough-in | 3/4/2020 | 3/4/2020 | 3/4/2020 | P | PASS |
Mike Jordan
|
|
|
2nd floor cloud ceiling framing for cover Phone #: ###-#### Inspection requested via web by Jared Waggoner
|
BLD-Wall Bracing | 2/17/2020 | 2/18/2020 | 2/18/2020 | A | FAIL |
Mike Jordan
|
|
|
Ist floor west exterior wall interior shear Phone #: ###-#### Inspection requested via web by Jared Waggoner. Engineer of record to provide alternate attachment details for areas that are inaccessable to provide attachments.
|
BLD-Framing/Rough-in | 2/12/2020 | 2/13/2020 | 2/13/2020 | A | PASS |
Mike Jordan
|
|
|
First floor suspended GWB ceiling and 2 exterior canopies for cover Phone #: ###-#### Inspection requested via web by Jared Waggoner
|
BLD-Wall Bracing | 2/10/2020 | 2/11/2020 | 2/11/2020 | A | PASS |
Mike Jordan
|
|
|
2nd floor east interior shear wall Phone #: ###-#### Inspection requested via web by Jared Waggoner
|
BLD-Energy code compliance | 2/10/2020 | 2/10/2020 | 2/10/2020 | A | PASS |
Mike Jordan
|
|
|
2nd floor E/W/S exterior wall insulation Phone #: ###-#### Inspection requested via web by Jared Waggoner. Remainder of 2nd floor exterior walls ok.
|
BLD-Energy code compliance | 2/7/2020 | 2/7/2020 | 2/7/2020 | P | PASS |
Mike Jordan
|
|
|
Foreman Phone #: ###-####. North exterior wall only ok.
|
Override - Parcel Holds | 2/7/2020 | 1/1/1900 | 2/7/2020 | | |
|
|
|
Per Bob A. override
|
BLD-Framing/Rough-in | 2/6/2020 | 2/6/2020 | 2/6/2020 | P | PASS |
Mike Jordan
|
|
|
2nd floor walls and ceilings for cover Phone #: ###-#### Inspection requested via web by Jared Waggoner
|
BLD-Framing/Rough-in | 2/3/2020 | 2/3/2020 | 2/3/2020 | P | PART |
Tony Young
|
|
|
Framing inspection for 1 side at interior 2nd floor walls Phone #: ###-#### Inspection requested via web by Jared Waggoner/// ok to one side from 10' up pending trades
|
BLD-Energy code compliance | 1/23/2020 | 1/24/2020 | 1/24/2020 | A | PASS |
Jim Storey
|
|
|
First floor wall insulation Phone #: ###-#### Inspection requested via web by Jared Waggoner
|
BLD-Framing/Rough-in | 1/22/2020 | 1/22/2020 | 1/22/2020 | P | PASS |
Mike Jordan
|
|
|
First floor rough framing for cover Phone #: ###-#### Inspection requested via web by Jared Waggoner. 1st. floor i nterior steel stud framed walls ok. hardlids ok pending mech. rough in inspection.
|
BLD-Wall Bracing | 1/13/2020 | 1/13/2020 | 1/13/2020 | P | PASS |
Mike Jordan
|
|
|
90% exterior sheet metal shear inspection Phone #: ###-#### Inspection requested via web by Jared Waggoner
|
Print Occupancy Form | | | 1/6/2020 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 1/6/2020 | | DONE |
|
|
|
|
Plan assigned to (JAR) | 12/20/2019 | 12/20/2019 | 1/2/2020 | | DONE |
Julie Romig
|
|
|
12/27 (5 days) - Plan Mod Amherst Madison
|
Routing - PLAN CHECK | 12/23/2019 | | 1/2/2020 | | PASS |
Julie Romig
|
|
|
|
Permit Ready to Issue | | | 1/2/2020 | | DONE |
|
|
|
**DO NOT REISSUE - PLAN MOD: IN EPLAN BLD18-04243
|
Routing - PLUMBING | 12/23/2019 | | 12/27/2019 | | PASS |
Dan Ediger
|
|
|
Plan Mod approved per Dan Ediger in ePlanReview
|
Routing - MECHANICAL | 12/23/2019 | | 12/23/2019 | | PASS |
Troy James
|
|
|
Plan Mods
|
Plan Modification Accepted | | | 12/20/2019 | | DONE |
|
|
|
Enlarge 2nd floor restrooms, add three interoffice doors, revise phone booth lights. (All electrical sheets are being resubmitted as the previous engineer left the firm.)
|
BLD-Concrete | 11/14/2019 | 11/15/2019 | 11/15/2019 | A | PART |
Mike Jordan
|
|
|
2nd floor slab on deck reinforcement Phone #: ###-#### Inspection requested via web by Jared Waggoner. 2nd. floor slab on deck. work in progress. Needs to install perimeter #4 bar and splice 15ft. at re-enterant corners. Special inspection to verify.
|
BLD-Other | 11/4/2019 | 11/4/2019 | 11/4/2019 | P | DEFR |
Mike Jordan
|
|
|
8" CMU grout at east patio walls at 2:30 pm 12''-16'', will have special inspection. Phone #: ###-#### Inspection requested via web by Jared Waggoner
|
BLD-Other | 10/31/2019 | 11/1/2019 | 11/1/2019 | P | PEND |
Mike Jordan
|
|
|
CMU grout from 8''-12'' at 1pm, will have special inspection Phone #: ###-#### Inspection requested via web by Jared Waggoner. PEnding special inspection.
|
BLD-Other | 10/30/2019 | 10/31/2019 | 10/31/2019 | P | PART |
Mike Jordan
|
|
|
4''-8'' CMU grout at 3pm, will have special inspection Phone #: ###-#### Inspection requested via web by Jared Waggoner. 4ft. to 8ft. elevation for CMU wall at patio.
|
BLD-Other | 10/30/2019 | 10/31/2019 | 10/31/2019 | A | DEFR |
Mike Jordan
|
|
|
0-4'' CMU grout at 10am, will have special inspection Phone #: ###-#### Inspection requested via web by Jared Waggoner
|
Print Occupancy Form | | | 10/21/2019 | | DONE |
|
|
|
|
BLD-Concrete | 10/16/2019 | 10/17/2019 | 10/17/2019 | P | PASS |
Mike Jordan
|
|
|
Slab on Grade Reinforcement Phone #: ###-#### Inspection requested via web by Jared Waggoner
|
BLD-Foundation | 9/27/2019 | 9/27/2019 | 9/27/2019 | P | PASS |
Brandon Shaw
|
|
|
Ok to place concrete pending special inspection.
|
BLD-Footing | 9/18/2019 | 9/18/2019 | 9/18/2019 | P | PART |
Mike Jordan
|
|
|
Call 30 minutes ahead // Jerrod Phone #: ###-####. Perimeter footings, column pad footings, interior footings and elevator and trash enclosure footings. Noted clearance issues in some areas. Special inspection agency to verify clearane issues have been repaired prior to conc. placement. Ok to place concrete pending special inspection.
|
Issue PAID IN FULL permit | | | 9/18/2019 | | DONE |
|
|
|
|
Plan assigned to (JAR) | 8/13/2019 | 8/13/2019 | 9/17/2019 | | DONE |
Julie Romig
|
|
|
1st Rev Comp - 4th Comp - Amherst Madision TI
|
Permit Ready to Issue | | | 9/17/2019 | | DONE |
|
|
|
please do not issue without BLD18-04243
|
Routing - PLAN CHECK | 9/10/2019 | | 9/17/2019 | | PASS |
Julie Romig
|
|
|
5th Review
|
Routing - PLUMBING | 9/11/2019 | | 9/11/2019 | | PASS |
Julie Romig
|
|
|
Passed per ePlanReview and BLD18-04243
|
Routing - PLAN CHECK | 8/22/2019 | | 9/9/2019 | | FAIL |
Julie Romig
|
|
|
4th Review
|
Routing Off Site - STRUCTURAL | 8/22/2019 | | 9/4/2019 | | PASS |
Julie Romig
|
|
|
AHJ - 3rd Review
|
Routing - PUBLIC WORKS | 8/22/2019 | | 8/23/2019 | | PASS |
Julie Romig
|
|
|
Passed per ePlanReview and BLD18-04243
|
Routing - PLUMBING | 8/22/2019 | | 8/22/2019 | | FAIL |
Julie Romig
|
|
|
failed per ePlanReview
|
Plan resubmittals received | | | 8/13/2019 | | |
|
|
|
resubmittal per Julie Romig
|
Extend Review Timeline | | | 5/24/2019 | | DONE |
|
|
|
1st approved 180 day extension per adele. see documents
|
Telephone call | | | 5/15/2019 | | DONE |
|
|
|
Marla Carson requested an extension, forward emailed to Adele.
|
Routing - Erosion and Sediment | 12/5/2018 | | 5/7/2019 | | PASS |
Andy J. Long
|
|
|
See ESC18-01466. Project already has ESC coverage. VOID
|
Routing - PLUMBING | 4/1/2019 | | 4/20/2019 | | PASS |
Daryl Spivey
|
|
|
1) provide tempered water to lavs as required by ISPC 407.3
2) Provide secondary roof drainage as required
|
Plan assigned to (JAR) | 12/5/2018 | 12/5/2018 | 4/19/2019 | | DONE |
Julie Romig
|
|
|
1st Rev Comp - 2nd Comp - 502 Amherst Madison Office TI
|
Routing - Design Review | 4/1/2019 | | 4/19/2019 | | PASS |
Katelyn Menuge
|
|
|
Redlined Changes
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/19/2019 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 4/19/2019 | | DONE |
|
|
|
still need ACHD-NEED
ACHD
REVISED VALUE-met
GC FORM-met
|
Routing - PLAN CHECK | 4/1/2019 | | 4/18/2019 | | FAIL |
Julie Romig
|
|
|
|
Routing - FIRE | 4/1/2019 | 4/1/2019 | 4/5/2019 | | PASS |
Erika Akin
|
|
|
Attached revised comments to case
|
Routing - MECHANICAL | 4/1/2019 | | 4/3/2019 | | PASS |
Troy James
|
|
|
|
Routing - PUBLIC WORKS | 4/1/2019 | | 4/2/2019 | | PASS |
Angela Hardy
|
|
|
WBSD
|
Routing Off Site - STRUCTURAL | 4/1/2019 | | 4/1/2019 | | PASS |
Julie Romig
|
|
|
|
Route to Impact Fee Review | 1/10/2019 | 1/13/2019 | 1/10/2019 | | PASS |
Eric Bilimoria
|
|
|
Review requested for Commercial Permit
|
1st review completed | | | 1/9/2019 | | FAIL |
Julie Romig
|
|
|
|
Routing - PLAN CHECK | 12/5/2018 | | 1/9/2019 | | FAIL |
Julie Romig
|
|
|
|
Routing - FIRE | 12/5/2018 | 12/5/2018 | 1/2/2019 | | FAIL |
Erika Akin
|
|
|
Attached comments to case and emailed architect
|
Routing Off Site - STRUCTURAL | 12/5/2018 | | 12/17/2018 | | FAIL |
Julie Romig
|
|
|
|
Routing - MECHANICAL | 12/5/2018 | | 12/13/2018 | | PASS |
Troy James
|
|
|
|
Intake Approval | | | 12/13/2018 | | PASS |
Julie Romig
|
|
|
Intake approval date of TI application submittal. Reviewed under shell/core permit BLD18-04243 in ePlan.
|
Routing - Design Review | 12/5/2018 | | 12/5/2018 | | FAIL |
Katelyn Menuge
|
|
|
See BLD18-04243
|
Routing - PLUMBING | 12/5/2018 | | 12/5/2018 | | PASS |
Daryl Spivey
|
|
|
1) provide tempered water to lavs as required by ISPC 407.3
2) Provide secondary roof drainage as required by ISPC.
|
Routing - Addressing | 12/5/2018 | | 12/5/2018 | | PASS |
Doug Chausow
|
|
|
|
Routing - PUBLIC WORKS | 12/5/2018 | | 12/5/2018 | | PASS |
Morgan Webb
|
|
|
|
Application received | | 12/5/2018 | | | |
|
|
|
|
Application received | | 12/5/2018 | | | |
|
|
|
|