Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberBLD19-01250
StatusReady to Issue
Name KINCAID CONSTRUCTION LLC
Site Address 999 W MAIN ST Unit: 110
Project NameKIN - Restaurant T.I.
Customer Number 
ePlanReviewYes
Description
(KIN) (DRH19-00100) **3RD PLAN MODFICATION 6-26-20 TO REMOVE GREEN ROOF FROM SCOPE OF PROJECT **2ND PLAN MODIFICATION 1-17-20 TO MODIFY EGRESS PLAN AND EXIT SIGN LOCATION **1ST PLAN MODIFICATION 12-4-19 to add a rooftop garden system at 1st floor patio/roof framing.**JHB** The fire sprinkler system is used for high rise and for fire area. To remodel a 6,981 square foot indoor/outdoor area formerly used by a bar and grill restaurant to an upscale dining establishment. The total area of the restaurant will be 6,981 square feet (5,135 square feet interior restaurant, 475 square feet interior shared restrooms, and 1,371 square feet exterior patio). There is no change to the occupancy. Work is to include interior nonbearing walls, wall furring, half-height walls, interior doors, exterior roof/wall area, dining booths, tables and chairs, fixed benches, drink dispensers, remodel to existing kitchen, new kitchen equipment, suspended acoustical ceilings, gypsum board ceilings and soffits, millwork, and finishes. **Special Inspections** are required for welding, intumescent coating for load bearing columns, and post-installed concrete anchors. The new roof construction has a 1.5 hour fire-resistance rating and new load bearing columns have a 2 hour fire-resistance rating. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **JHB**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
OVERRIDE  6/29/2020  
OVERRIDE  6/29/2020  
Plan assigned to (Joe)6/22/20206/22/20206/29/2020 PASS
DetailsJoe Bruce
07/01 plan mod #3- Remove green rood from project- plan mod fee sheet in Eplan
Permit Ready to Issue  6/29/2020 DONE
NEED UPDATED VALUE
Plan mod
Routing - Design Review6/26/2020 6/26/2020 PASS
DetailsKatelyn Menuge
Green Roof Removal okay.
Routing - PLAN CHECK6/26/2020 6/26/2020 PASS
DetailsJoe Bruce
Plan mod to remove green roof has been passed.
Plan Reviewer's activity  6/24/2020 DONE
DetailsJoe Bruce
Prescreen accepted for plan mod to remove green roof. **JHB**
Plan Modification Accepted  6/22/2020 DONE
plan mod #3
BLD-Final6/12/20206/12/20206/17/2020PPART
DetailsDave Hannah
Zach - *Screened* Phone #: ###-#### rest rooms ok
Temporary Occupancy6/8/20209/6/20206/8/2020 DONE
DetailsBrittany Hill
Zoning Approval Temp6/8/20206/8/20206/8/2020 PASS
DetailsKatelyn Menuge
Temporary - Will need to complete exterior work on patio and roof garden prior to final
BLD-Final3/24/20203/24/20203/24/2020PNR
DetailsDave Hannah
Zack Phone #: ###-####
FIRE-Final Inspection3/24/20203/24/20203/24/2020PPART
DetailsJim Page
Public restrooms off of common corridor are attached to this permit, final life fire safety inspection for public restrooms complete, permit will remain in issued status until all life fire safety items are complete with restaurant TI.

Zack Phone #: ###-####
BLD-Final3/19/20203/20/20203/20/2020PPART
DetailsDave Hannah
is there a fire, life , safety inspection other than the final? Phone #: ###-#### Inspection requested via web by Larry Kincaid ok to use kitchen an bar on tco
BLD-Other3/20/20203/20/20203/20/2020PCANC
DetailsDave Hannah
need fire life safety inspection Phone #: ###-#### Inspection requested via web by Larry Kincaid
FIRE-Final Inspection3/20/20203/20/20203/20/2020PPART
DetailsJim Page
Final life fire safety inspection for TCO phase 1 is complete.

Plan Reviewer's activity  3/3/2020 DONE
DetailsJoe Bruce
Recevied email from CDHD (Scott Paradis) regarding the approval of KIN restaurant. Upload email into documents. Okay to issue CO without health department signature on card. **JHB**
BLD-Ceiling Grid Inspection2/25/20202/26/20202/28/2020APASS
DetailsDave Hannah
Zach Phone #: ###-####
BLD-Ceiling Grid Inspection2/18/20202/19/20202/19/2020APART
DetailsDave Hannah
Inspection requested via web by Larry Kincaid ok to cover kitchen area
CHANGE STATUS TO (ISS)  2/6/2020 DONE
OVERRIDE  1/24/2020  
Plan assigned to (Joe)1/16/20201/16/20201/24/2020 PASS
DetailsJoe Bruce
2nd plan mod KIN
Routing - PLAN CHECK1/17/2020 1/24/2020 PASS
DetailsJoe Bruce
Plan Mod Passed for modified exit/egress plan. JHB
Permit Ready to Issue  1/24/2020 DONE
DO NOT ISSUE- plan mod 2 approved
BLD-Framing/Rough-in1/21/20201/21/20201/21/2020PPASS
DetailsDave Hannah
Zack Phone #: ###-####
Plan Modification Accepted  1/16/2020 DONE
Cathy Sewell of platform architects requested a plan mod workflow. Revise exiting requirements.
Sheets to be uploaded: G0.1, E2.2, E4.0
BLD-Ceiling Grid Inspection1/13/20201/13/20201/14/2020PPART
DetailsDave Hannah
Larry Phone #: ###-#### cielings above entry doors
CHANGE STATUS TO (ISS)  12/17/2019 DONE
OVERRIDE  12/4/2019  
Plan assigned to (Joe)11/5/201911/5/201912/4/2019 PASS
DetailsJoe Bruce
(plan mod) KIN Restaurant
Plan resubmittals received  12/4/2019 DONE
DetailsJoe Bruce
Routing - PLAN CHECK12/4/2019 12/4/2019 PASS
DetailsJoe Bruce
Strucutural Calcs have been revised to show the proper live and dead loads.
Permit Ready to Issue  12/4/2019 DONE
**DO NOT REISSUE - PLAN MOD**
Routing - FIRE11/25/201911/25/201911/29/2019 PASS
DetailsJoe Bruce
Requirements of 2015 IFC 317 have been met for rooftop gardens and landscaped roofs.
Plan resubmittals requested  11/29/2019 DONE
DetailsJoe Bruce
Plan mod requires additional information for a resubmittal.
Routing - PLAN CHECK11/25/2019 11/29/2019 FAIL
DetailsJoe Bruce
See page 12 of the revised structural calculations for corrections required to the dead and live load calculations.
Routing - Design Review11/25/2019 11/26/2019 PASS
DetailsKatelyn Menuge
Redlined DR requirements.
Plan Modification Accepted  11/5/2019 DONE
Cathy Sewell from Platform Architecture requested to start a plan mod workflow. Install green roof system. Sheet A3.1
BLD-Framing/Rough-in10/27/201910/28/201910/28/2019APASS
DetailsMike Jordan
requesting framing inspection at new canopy Phone #: ###-#### Inspection requested via web by Larry Kincaid
BLD-Framing/Rough-in10/22/201910/23/201910/23/2019APASS
DetailsDave Hannah
Inspection requested via web by Larry Kincaid
BLD-Foundation9/6/20199/9/20199/9/2019APASS
DetailsDave Hannah
Pour is early in the morning. Please come as early as possible Inspection requested via web by Larry Kincaid
BLD-Foundation9/6/20199/6/20199/6/2019PCANC
DetailsDave Hannah
Please come later in the day if possible we are trying to get ready for a Monday am pour Thank you >> Inspection requested via web by Larry Kincaid Inspection cancelled from web by: Larry Kincaid
BLD-Footing8/28/20198/29/20198/29/2019APASS
DetailsDave Hannah
Inspection requested via web by Larry Kincaid
Issue PAID IN FULL permit  7/18/2019 DONE
Print Occupancy Form  7/18/2019 DONE
Print Occupancy Form  7/17/2019 DONE
OVERRIDE  6/13/2019  
Plan assigned to (JHB)4/29/20194/29/20196/13/2019 PASS
DetailsJoe Bruce
06/14 (2nd Rev) 05/23 (L3) Kin Restaurant, ePlan
Routing - PLAN CHECK6/10/2019 6/13/2019 PASS
DetailsJoe Bruce
PLANS/APPL TAKEN TO FRONT DESK  6/13/2019 DONE
Permit Ready to Issue  6/13/2019 DONE
All Met

Need
GC Form
Rev Valule
RP
Routing - PLUMBING6/10/2019 6/10/2019 PASS
DetailsDaryl Spivey
Per plan and ISPC
Routing - Design Review6/10/2019 6/10/2019 PASS
DetailsKatelyn Menuge
Planter change is approved.
Plan resubmittals received  6/7/2019 DONE
DetailsJoe Bruce
Route to Impact Fee Review5/23/20195/26/20195/24/2019 PASS
DetailsKarina Myles
Review requested for Commercial Permit
1st review completed  5/23/2019 FAIL
DetailsJoe Bruce
Plan resubmittals requested  5/23/2019 DONE
DetailsJoe Bruce
emailed architect plan review report.
Routing - PLAN CHECK4/29/2019 5/23/2019 FAIL
DetailsJoe Bruce
Routing - FIRE4/29/20194/29/20195/22/2019 PASS
DetailsMark Scharfen
Completed fire review and uploaded rev_fire 05.22.2019.pdf. Passed review.
Routing - MECHANICAL4/29/2019 5/7/2019 PASS
DetailsTroy James
Routing PW Environmental4/30/2019 5/2/2019 PASS
DetailsRick Christenson
Routing - Erosion and Sediment5/2/2019 5/2/2019 PASS
DetailsMichael Zawacki
Waiver approved, states that total commercial disturbance will be less than 10 cubic yards.
Routing - PLUMBING4/29/2019 5/1/2019 PASS
DetailsDaryl Spivey
See redline on G/I venting. Install per plan and ISPC.
Routing - Addressing4/29/2019 4/30/2019 PASS
DetailsDoug Chausow
Routing - PUBLIC WORKS4/29/2019 4/30/2019 PASS
DetailsMorgan Webb
NO NEW FEES. NO ADDITION OF CUSTOMER SERVICE AREA.
Routing - Design Review4/29/2019 4/30/2019 PASS
DetailsKatelyn Menuge
DRH19-00100
Routing Off Site - C.D.H4/29/2019 4/30/2019 PASS
DetailsJoe Bruce
CDHD pass.
Intake Approval  4/26/2019 PASS
Intake Approval  4/19/2019 FAIL
DetailsJulie Romig
Need Sheet A8.0 with door/hardware schedule and accessibility info.
Application received  4/18/2019 DONE
Application submitted via PDS Online on Apr 18 2019 7:07AM